Especificaciones técnicas
Protección y seguridad
| Reverse polarity protection | Yes |
|---|---|
| Short-circuit protection | Yes; Electronic |
| Short-circuit to ground | Yes; module-by-module for DQ |
| Short-circuit to L+ | Yes; module-by-module for DQ |
| Isolation tested with | 707 V DC (type test) |
Datos eléctricos
| Current consumption, max. | 35 mA; without load |
|---|---|
| Power loss, typ. | 1W |
| Current-sourcing | Yes |
| Limitation of inductive shutdown voltage to | Typ. L+ (-50 V) |
| for signal "0" residual current, max. | 0.1 mA |
| Current per channel, max. | 0.5 A |
| Current per module, max. | 4A |
| permissible quiescent current (2-wire sensor), max. | 1.5 mA |
| Monitoring the supply voltage | Yes |
| Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Entradas/Salidas y comunicación
| PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
|---|---|
| PROFINET from GSD version/GSD revision | GSDML V2.42 |
Detección y sensórica
| 2-wire sensor | Yes |
|---|
Montaje y material
| Color code for module-specific color-coded label | CC00 |
|---|
Certificados y homologaciones
| Type Examination Cer | CCC-Ex |
|---|
Otras características
| Product type designation | DI 8x/DQ 8x24VDC/0,5A ST |
|---|---|
| HW functional status | FS01 |
| Firmware version | V1.0 |
| FW update possible | Yes |
| usable BaseUnits | BU type A0 |
| I&M data | Yes; I&M0 to I&M3 |
| STEP 7 TIA Portal configurable/integrated from version | STEP 7 V18 or higher with HSP 0401 |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Inputs | 1 byte; + 1 byte for QI information |
| Outputs | 1 byte |
| Automatic encoding | Yes |
| Mechanical coding element | Yes |
| Type of mechanical coding element | Type A |
| 1-wire connection | BU type A0 |
| 2-wire connection | BU type A0 with AUX terminals or potential distributor module |
| 3-wire connection | BU type A0 with AUX terminals or potential distributor module |
| Number of digital inputs | 8 |
| Digital inputs, parameterizable | Yes |
| Sourcing/sinking input | P-reading |
| for signal "0" | -30 to +5 V |
| for signal "1" | +11 to +30V |
| for signal "1", typ. | 2.5 mA |
| parameterizable | Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms |
| shielded, max. | 1 000 m |
| unshielded, max. | 600 m |
| Type of digital output | Source output (PNP, current-sourcing) |
| Number of digital outputs | 8 |
| Digital outputs, parameterizable | Yes |
| output type acc. to IEC 61131, type 0.5 | Yes |
| Response threshold, typ. | 1A |
| Controlling a digital input | Yes |
| lower limit | 48 Ω |
| upper limit | 12 kΩ |
| for signal "1", min. | L+ (-0.8 V) |
| for signal "1" rated value | 0.5 A |
| for signal "1" permissible range, max. | 0.5 A |
| "0" to "1", max. | 50 µs |
| "1" to "0", max. | 100 µs |
| for redundant control of a load | Yes |
| up to 60 °C, max. | 4A |
| up to 50 °C, max. | 4A |
| Diagnostics function | Yes |
| Substitute values connectable | Yes |
| Diagnostic alarm | Yes |
| Group error | Yes |
| Channel status display | Yes; green LED |
| for module diagnostics | Yes; green/red DIAG LED |
| between the channels and backplane bus | Yes |
| horizontal installation, min. | -30 °C |
| horizontal installation, max. | 60 °C |
| vertical installation, min. | -30 °C |
| vertical installation, max. | 50 °C |
| dew point, min. | -60 °C; suitable for dry room applications |
| Width | 15 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Weight, approx. | 30 g |
| For use in hazardous locations | Maritime application |
| tificate | okai |
| last modified: | 2/1/2026 |