Especificaciones técnicas
Protección y seguridad
| Short-circuit protection | No; external fusing necessary |
|---|---|
| Isolation tested with | 2 545 V DC/2 s (routine test) |
| Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
Datos eléctricos
| Current consumption (rated value) | 8 mA; without load |
|---|---|
| Current-sourcing | Yes |
| for signal "0" residual current, max. | 3 mA |
| Current per channel, max. | 2 A; Max. 4 A, see additional description in manual |
| Current per module, max. | 8A |
| Monitoring the supply voltage | Yes |
| Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Montaje y material
| Color code for module-specific color-coded label | CC20 |
|---|
Condiciones ambientales
| Installation altitude above sea level, max. | 2 000 m |
|---|---|
| Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) |
Otras características
| Product type designation | DQ 4x24 ... 230 V AC/2 A HF |
|---|---|
| FW update possible | Yes |
| based on | 6ES7132-6FD00-0CU0 |
| usable BaseUnits | BU type U0 |
| I&M data | Yes; I&M0 to I&M3 |
| STEP 7 TIA Portal configurable/integrated from version | see entry ID: 109746275 |
| DQ with energy-saving function | Yes |
| Phase control | Yes; Control area: 8.5 ... 100% of the phase angle |
| Half-wave | Yes |
| Full-wave | Yes |
| Rated value (AC) | 230 V; 47 ... 63 Hz, max. rate of change of frequency 1 mHz/s |
| permissible range, lower limit (AC) | 20.4 V |
| permissible range, upper limit (AC) | 264 V |
| Inputs | + 1 byte for QI information |
| Outputs | 8 byte |
| Automatic encoding | Yes |
| Mechanical coding element | Yes |
| Type of mechanical coding element | type C |
| 1-wire connection | BU type U0 |
| 2-wire connection | BU type U0 |
| 3-wire connection | BU type U0 + Potential distributor module |
| Type of digital output | Triac |
| Number of digital outputs | 4 |
| Digital outputs, parameterizable | Yes |
| Open-circuit detection | Yes; channel by channel |
| Response threshold, typ. | 1 mA; 40 V AC or more |
| Controlling a digital input | Yes |
| for signal "1", min. | 20.4 V |
| for signal "1" rated value | 2A |
| for signal "1" permissible range, min. | 10 mA |
| for signal "1" permissible range, max. | 4 A; note derating data in the manual |
| "0" to "1", max. | 40 ms; 2 AC cycles |
| "1" to "0", max. | 20 ms; 1 AC cycle |
| for redundant control of a load | Yes |
| up to 70 °C, max. | 2 A; Applicable for current channels up to 2 A |
| up to 30 °C, max. | 8A |
| up to 40 °C, max. | 6A |
| up to 50 °C, max. | 4A |
| shielded, max. | 1 000 m |
| unshielded, max. | 600 m |
| Diagnostics function | Yes |
| Substitute values connectable | Yes |
| Diagnostic alarm | Yes |
| Diagnostic information readable | Yes |
| Wire break | Yes; channel by channel |
| Group error | Yes |
| Channel status display | Yes; green LED |
| for channel diagnostics | Yes; red Fn LED |
| for module diagnostics | Yes; green/red DIAG LED |
| between the channels and backplane bus | Yes |
| horizontal installation, min. | -40 °C; = Tmin (incl. condensation/frost) |
| horizontal installation, max. | 70 °C; = Tmax |
| vertical installation, min. | -40 °C; = Tmin |
| vertical installation, max. | 50 °C; = Tmax |
| 2-38, max. | horizontal installation |
| Resistant to commercially available coolants and | Yes; Incl. diesel and oil droplets in the air |
| 60721-3-3 | Class 3B3 on request |
| to EN 60721-3-3 | 0AA0) |
| 60721-3-6 | degree 3); * |
| to EN 60721-3-6 | 0AA0) |
| conditions acc. to EN 60721, EN 60654-4 and | during operation! |
| Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
| Qualification and Performance of Electrical Insulating | Yes; Conformal coating, Class A |
| Width | 20 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Weight, approx. | 50 g |
| EMV | Maritime application |
| last modified: | 7/9/2025 |