| product brand name | SIRIUS |
|---|
| product category | Hybrid switching devices |
|---|
| product type designation | 3RW52 |
|---|
| of standard HMI module usable | 3RW5980-0HS00 |
|---|
| of high feature HMI module usable | 3RW5980-0HF00 |
|---|
| of circuit breaker usable at 400 V | 3RV2032-4EA10; Type of coordination 1, Iq = 65 kA, CLASS 10 |
|---|
| of circuit breaker usable at 500 V | 3RV2032-4EA10; Type of coordination 1, Iq = 15 kA, CLASS 10 |
|---|
| of the gG fuse usable up to 690 V | 3NA3822-6; Type of coordination 1, Iq = 65 kA |
|---|
| of full range R fuse link for semiconductor protection | 3NE1817-0; Type of coordination 2, Iq = 65 kA |
|---|
| of back-up R fuse link for semiconductor protection | 3NE8021-1; Type of coordination 2, Iq = 65 kA |
|---|
| starting voltage [%] | 30 ... 100 % |
|---|
| stopping voltage [%] | 50 %; non-adjustable |
|---|
| start-up ramp time of soft starter | 0 ... 20 s |
|---|
| current limiting value [%] adjustable | 130 ... 700 % |
|---|
| CE marking | Yes |
|---|
| UL approval | Yes |
|---|
| CSA approval | Yes |
|---|
| is supported HMI-Standard | Yes |
|---|
| is supported HMI-High Feature | Yes |
|---|
| product feature integrated bypass contact system | Yes |
|---|
| number of controlled phases | 3 |
|---|
| for main current circuit | 100 ms |
|---|
| for control circuit | 100 ms |
|---|
| insulation voltage rated value | 600 V |
|---|
| degree of pollution | 3, acc. to IEC 60947-4-2 |
|---|
| impulse voltage rated value | 6 kV |
|---|
| blocking voltage of the thyristor maximum | 1 600 V |
|---|
| service factor | 1 |
|---|
| surge voltage resistance rated value | 6 kV |
|---|
| between main and auxiliary circuit | 600 V |
|---|
| shock resistance | 15 g / 11 ms, from 12 g / 11 ms with potential contact lifting |
|---|
| vibration resistance | 15 mm to 6 Hz; 2 g to 500 Hz |
|---|
| utilization category according to IEC 60947-4-2 | AC 53a |
|---|
| Net Weight | 2.93 kg |
|---|
| ramp-up (soft starting) | Yes |
|---|
| soft stopping | Yes |
|---|
| Soft Torque | Yes |
|---|
| adjustable current limitation | Yes |
|---|
| pump stop | Yes |
|---|
| intrinsic device protection | Yes |
|---|
| motor overload protection | Yes; Electronic motor overload protection |
|---|
| inside-delta circuit | Yes |
|---|
| auto-RESET | Yes |
|---|
| manual RESET | Yes |
|---|
| remote reset | Yes; By turning off the control supply voltage |
|---|
| communication function | Yes |
|---|
| operating measured value display | Yes; Only in conjunction with special accessories |
|---|
| error logbook | Yes; Only in conjunction with special accessories |
|---|
| via software configurable | Yes |
|---|
| PROFIenergy | Yes; in connection with the PROFINET Standard communication module |
|---|
| firmware update | Yes |
|---|
| at 40 °C rated value | 25 A |
|---|
| at 50 °C rated value | 22.3 A |
|---|
| at 60 °C rated value | 19.6 A |
|---|
| rated value | 200 ... 600 V |
|---|
| at inside-delta circuit rated value | 200 ... 600 V |
|---|
| relative negative tolerance of the operating voltage | -15 % |
|---|
| relative positive tolerance of the operating voltage | 10 % |
|---|
| relative negative tolerance of the operating voltage at | -15 % |
|---|
| relative positive tolerance of the operating voltage at | 10 % |
|---|
| at 230 V at 40 °C rated value | 5.5 kW |
|---|
| at 230 V at inside-delta circuit at 40 °C rated value | 11 kW |
|---|
| at 400 V at 40 °C rated value | 11 kW |
|---|
| at 400 V at inside-delta circuit at 40 °C rated value | 18.5 kW |
|---|
| at 500 V at 40 °C rated value | 15 kW |
|---|
| at 500 V at inside-delta circuit at 40 °C rated value | 22 kW |
|---|
| Operating frequency 1 rated value | 50 Hz |
|---|
| Operating frequency 2 rated value | 60 Hz |
|---|
| relative negative tolerance of the operating frequency | -10 % |
|---|
| relative positive tolerance of the operating frequency | 10 % |
|---|
| at rotary coding switch on switch position 1 | 11.5 A |
|---|
| at rotary coding switch on switch position 2 | 12.4 A |
|---|
| at rotary coding switch on switch position 3 | 13.3 A |
|---|
| at rotary coding switch on switch position 4 | 14.2 A |
|---|
| at rotary coding switch on switch position 5 | 15.1 A |
|---|
| at rotary coding switch on switch position 6 | 16 A |
|---|
| at rotary coding switch on switch position 7 | 16.9 A |
|---|
| at rotary coding switch on switch position 8 | 17.8 A |
|---|
| at rotary coding switch on switch position 9 | 18.7 A |
|---|
| at rotary coding switch on switch position 10 | 19.6 A |
|---|
| at rotary coding switch on switch position 11 | 20.5 A |
|---|
| at rotary coding switch on switch position 12 | 21.4 A |
|---|
| at rotary coding switch on switch position 13 | 22.3 A |
|---|
| at rotary coding switch on switch position 14 | 23.2 A |
|---|
| at rotary coding switch on switch position 15 | 24.1 A |
|---|
| at rotary coding switch on switch position 16 | 25 A |
|---|
| minimum | 11.5 A |
|---|
| at inside-delta circuit minimum | 19.9 A |
|---|
| minimum load [%] | 15 %; Relative to smallest settable Ie |
|---|
| at 40 °C after startup | 20 W |
|---|
| at 50 °C after startup | 19 W |
|---|
| at 60 °C after startup | 18 W |
|---|
| at 40 °C during startup | 376 W |
|---|
| at 50 °C during startup | 318 W |
|---|
| at 60 °C during startup | 278 W |
|---|
| type of voltage of the control supply voltage | AC |
|---|
| at 50 Hz | 110 ... 250 V |
|---|
| at 60 Hz | 110 ... 250 V |
|---|
| control supply voltage frequency | 50 ... 60 Hz |
|---|
| control supply current in standby mode rated value | 30 mA |
|---|
| holding current in bypass operation rated value | 75 mA |
|---|
| inrush current by closing the bypass contacts maximum | 0.17 A |
|---|
| design of the overvoltage protection | Varistor |
|---|
| number of digital inputs | 1 |
|---|
| number of digital outputs | 3 |
|---|
| not parameterizable | 2 |
|---|
| digital output version | 2 normally-open contacts (NO) / 1 changeover contact (CO) |
|---|
| number of analog outputs | 1 |
|---|
| at AC-15 at 250 V rated value | 3A |
|---|
| at DC-13 at 24 V rated value | 1A |
|---|
| fastening method | screw fixing |
|---|
| height | 275 mm |
|---|
| width | 170 mm |
|---|
| depth | 152 mm |
|---|
| forwards | 10 mm |
|---|
| backwards | 0 mm |
|---|
| upwards | 100 mm |
|---|
| downwards | 75 mm |
|---|
| at the side | 5 mm |
|---|
| solid | 2x (1.0 ... 2.5 mm²), 2x (2.5 ... 10 mm²) |
|---|
| finely stranded with core end processing | 2x (1.0 ... 2.5 mm²), 2x (2.5 ... 6.0 mm²) |
|---|
| for control circuit solid | 2x (0.25 ... 1.5 mm²) |
|---|
| between soft starter and motor maximum | 800 m |
|---|
| at the digital inputs at AC maximum | 100 m |
|---|
| for auxiliary and control contacts with screw-type | 0.8 ... 1.2 N·m |
|---|
| during storage and transport | -40 ... +80 °C |
|---|
| during transport according to IEC 60721 | 2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m) |
|---|
| EMC emitted interference | acc. to IEC 60947-4-2: Class A |
|---|
| usable for Standard Faults up to 575/600 V | Type: Class RK5 / K5, max. 100 A; Iq = 5 kA |
|---|
| usable for High Faults up to 575/600 V according to | Type: Class J / L, max. 100 A; Iq = 100 kA |
|---|
| usable for Standard Faults at inside-delta circuit up | Type: Class RK5 / K5, max. 100 A; Iq = 5 kA |
|---|
| usable for High Faults at inside-delta circuit up to | Type: Class J / L, max. 100 A; Iq = 100 kA |
|---|
| at 200/208 V at 50 °C rated value | 5 hp |
|---|
| at 220/230 V at 50 °C rated value | 7.5 hp |
|---|
| at 460/480 V at 50 °C rated value | 15 hp |
|---|
| at 575/600 V at 50 °C rated value | 20 hp |
|---|
| contact rating of auxiliary contacts according to UL | R300-B300 |
|---|
| protection class IP on the front according to IEC 60529 | IP20 |
|---|
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front |
|---|
| 1/L1 | 3/L2 |
|---|
| 5/L3 | A1 |
|---|
| ON/RUN | BYPASSED |
|---|
| 13 NO | 23 NO |
|---|
| 98 NO | 96 NC |
|---|
| last modified: | 4/4/2026 |
|---|