ET 200SP, IM 155-6 PN ST incl. BA 2xRJ45
Siemens

ET 200SP, IM 155-6 PN ST incl. BA 2xRJ45

SIMATIC ET 200SP, bundle módulo de interfaz PROFINET IM 155-6 PN ST, máx. 32 módulos de periferia, y 16 módulos ET 200AL, Multi Hot Swapping, alivio de tracción PN opcional, PN Security Class 1, bundle compuesto por: módulo de interfaz (6ES7155-6AU02-0BN0), módulo de servidor (6ES7193-6PA00-0AA0), SIMATIC BusAdapter BA 2x RJ45 (6ES7193-6AR00-0AA0)

🔌 ComunicaciónGSDML V2.45
Entradas/Salidas y comunicación
PROFINET from GSD version/GSD revisionGSDML V2.45
Number of PROFINET interfaces1; 2 ports (switch)
RJ 45 (Ethernet)Yes; with BusAdapter
BusAdapter (PROFINET)Yes; BA 2x RJ45, BA 2x FC, BA 2x M12
PROFINET IO deviceYes
Supports protocol for PROFINET IOYes
PROFIsafeYes
between PROFINET and all other circuitsYes; 1500 V AC (type test)
PROFINET Security Class1
Otras características
Product type designationIM 155-6 PN ST incl. BA 2x RJ45 and server module
Firmware versionV6.4.0
FW update possibleYes
Vendor identification (VendorID)002AH
Device identifier (DeviceID)0313H
Device ID according to ODVA (Product code)0FA2H
I&M dataYes; I&M0 to I&M4
Module swapping during operation (hot swapping)Yes; Multi-hot swapping
IRTYes
Local coupling, IO dataYes
Number of coupling modules6; 1x output + max. 5x input
STEP 7 TIA Portal configurable/integrated from versionV20
STEP 7 configurable/integrated from versionV5.7 SP3
via datasetYes
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Short-circuit protectionYes
Mains/voltage failure stored energy time10 ms
Current consumption (rated value)350 mA
Current consumption, max.450 mA
Inrush current, max.1A
I²t0.05 A²·s
Power loss, typ.1.8 W
Address space per module, max.288 byte; For input and output data respectively
Address space per station, max.1 440 byte
Quantity of operable ET 200SP modules, max.32
Quantity of operable ET 200AL modules, max.16
Number of submodules per station, max.256
Transmission procedure100BASE-TX
Number of ports2; with BusAdapter
integrated switchYes
Open IE communicationYes
Media redundancyYes; PROFINET MRP client
Dynamic Frame Packing (DFP)Yes
Fast ForwardingYes
FragmentationYes
PROFIenergyYes
Prioritized startupYes
Shared deviceYes
Number of IO Controllers with shared device, max.4
100 MbpsYes
AutonegotiationYes
AutocrossingYes
MRPYes
MRPDYes
TCP/IPYes
UDPYes
SNMPYes
LLDPYes
ARPYes
IGMPYes
MulticastYes
BroadcastYes
IPv4Yes
Status indicatorYes
AlarmsYes
Diagnostics functionYes
RUN LEDYes; green LED
ERROR LEDYes; red LED
MAINT LEDYes; Yellow LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Connection display LINK TX/RXYes; 2x green link LEDs on BusAdapter
between different circuitsSafety extra low voltage SELV
Isolation tested with707 V DC (type test)
Network loading class3
signed firmware updateYes
safely removing dataYes
data integrityYes
horizontal installation, min.-30 °C; No condensation
horizontal installation, max.60 °C
vertical installation, min.-30 °C; No condensation
vertical installation, max.50 °C
dew point, min.-60 °C; suitable for dry room applications
via BU/BA SendYes; + 16 ET 200AL modules
Strain reliefYes; Optional
Width50 mm
Height117 mm
Depth74 mm
Weight, approx.120 g; without BusAdapter
last modified:6/18/2026
⬇ Descargar datasheet (PDF)

Ficha técnica oficial del fabricante con todas las especificaciones.

Material con posibilidad de devolución
ET 200SP, IM 155-6 PN ST incl. BA 2xRJ45
€388,87 EUR
€457,50 EUR
6ES7155-6AA02-0BN0
Plazo de entrega (días):
€388,87 EUR /cada
Total:

Accesorios