Especificaciones técnicas
Datos eléctricos
| Type of supply voltage | DC |
|---|---|
| Current consumption (rated value) | 0.7 A |
| Current consumption, max. | 1.3 A |
| Starting current inrush I²t | 0.5 A²·s |
Entradas/Salidas y comunicación
| Number of industrial Ethernet interfaces | 2; 2 ports (switch) + independent port |
|---|---|
| Number of RS 485 interfaces | 1; RS 422 / 485 combined |
| Number of RS 422 interfaces | 0; together with RS 485 |
| Number of USB interfaces | 4; USB 3.1 Gen. 1 (type A) |
| Industrial Ethernet status LED | 2 |
| PROFINET | Yes |
| Ethernet | Yes |
| Allen Bradley (EtherNet/IP) | Yes |
| Modicon (Modbus TCP/IP) | Yes |
| Modicon (Modbus RTU) | Yes |
| OPC UA Client | Yes |
| OPC UA Server | Yes |
Montaje y material
| Number of colors | 16 777 216 |
|---|
Prestaciones y durabilidad
| MTBF backlighting (at 25 °C) | 50 000 h |
|---|
Certificados y homologaciones
| CE mark | Yes |
|---|---|
| UKCA mark | Yes |
| cULus | Yes |
| RCM (formerly C-TICK) | Yes |
| KC approval | Yes |
| EAC (formerly Gost-R) | Yes |
| CCC | Yes |
| ATEX Zone 2 | Yes |
| ATEX Zone 22 | Yes |
| IECEx Zone 2 | Yes |
| IECEx Zone 22 | Yes |
| cULus Class I Zone 2, Division 2 | Yes |
| cULus Class II Division 2 | Yes |
| FM Class I Division 2 | Yes |
| FM Class II Division 2 | Yes |
| Germanischer Lloyd (GL) | No; included in DNV |
| American Bureau of Shipping (ABS) | Yes |
| Bureau Veritas (BV) | Yes |
| Det Norske Veritas (DNV) | Yes |
| Lloyds Register of Shipping (LRS) | Yes |
| China RoHS | Miscellaneous |
Otras características
| Product type designation | MTP1500 Unified Comfort |
|---|---|
| Design of display | TFT |
| Screen diagonal | 15.6 in |
| Display width | 344.2 mm |
| Display height | 197 mm |
| Horizontal image resolution | 1 366 pixel |
| Vertical image resolution | 768 pixel |
| Backlight dimmable | Yes; 10 ... 100% |
| Numeric keyboard | Yes; Onscreen keyboard |
| alphanumeric keyboard | Yes; Onscreen keyboard |
| Design as touch screen | Yes |
| Design as multi-touch screen | Yes |
| Mounting position | vertical |
| Mounting in portrait format possible | Yes |
| Mounting in landscape format possible | Yes |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Flash | Yes |
| RAM | Yes |
| Buzzer | Yes |
| Hardware clock (real-time) | Yes |
| Software clock | Yes |
| retentive | Yes; Back-up duration typically 6 weeks |
| synchronizable | Yes |
| Number of SD card slots | 2 |
| Number of ports of the integrated switch | 2 |
| TCP/IP | Yes |
| DHCP | Yes |
| SNMP | Yes |
| DCP | Yes |
| LLDP | Yes |
| MRP | Yes |
| Limit class A, for use in industrial areas | Yes |
| IP (at the front) | IP65 |
| IP (rear) | IP20 |
| Enclosure Type 4x at the front | Yes |
| Enclosure Type 12 at the front | Yes |
| Korean Register of Shipping (KRS) | Yes |
| Nippon Kaiji Kyokai (Class NK) | Yes |
| Chinese Classification Society (CCS) | Yes |
| Suited for indoor use | Yes |
| For vertical installation, min. | 0 °C |
| For vertical installation, max. | 50 °C |
| min. | -20 °C |
| max. | 60 °C |
| Operation, max. | 90 %; no condensation |
| proprietary | Yes |
| Message indicator | Yes |
| Alarm system (incl. buffer and acknowledgment) | Yes |
| Process value display (output) | Yes |
| Process value default (input) possible | Yes |
| Recipe management | Yes |
| WinCC Unified Comfort Engineering (TIA Portal) | Yes |
| WinCC Unified PC Engineering (TIA Portal) | Yes |
| Number of online/runtime languages | 32 |
| Languages per project | 32 |
| Libraries | Yes |
| Writer | Yes |
| Calc | Yes |
| Web browser | Yes |
| PDF Viewer | Yes |
| Media Player | Yes |
| SIMATIC WinCC Sm@rtServer | Yes |
| SIMATIC WinCC Audit | Yes |
| Unified Collaboration | Yes |
| JavaScript | Yes |
| time-controlled | Yes |
| task-controlled | Yes |
| Number of characters per info text | 70 |
| Number of message texts per message | 10 |
| Number of alarm classes | 32 |
| Number of bit messages | 9 000 |
| Number of analog messages | 300 |
| S7 alarm number procedure | Yes |
| System messages HMI | Yes |
| System event, more (SIMATIC S7, SINUMERIK, | Yes |
| Number of characters per message | 512 |
| Number of process values per message | 10 |
| Acknowledgment groups | Yes |
| Message buffer | Yes; Configured as alarm archive |
| Circulating buffer | Yes |
| maintenance-free | Yes |
| Number of parameter set types | 750 |
| Parameter sets per parameter set type | 2 000 |
| Entries per parameter set | 4 000; as of WinCC Unified V20 |
| Size of internal parameter set memory | 12 Mbyte |
| Parameter set memory expandable | Yes |
| Number of variables per device | 8 000 |
| Number of variables per screen | 800 |
| Limit values | Yes |
| Structures | Yes |
| Arrays | Yes |
| Number of configurable images | 1 200 |
| Faceplate | Yes |
| Number of objects per image | 1 200 |
| Picture window | Yes |
| Text fields | Yes |
| I/O fields | Yes |
| Graphic I/O fields (graphics list) | Yes |
| Symbolic I/O fields (text list) | Yes |
| Scalable Vector Graphics (SVG) | Yes |
| Date/time fields | Yes |
| Checkbox | Yes |
| Option button | Yes |
| Switches | Yes |
| Buttons | Yes |
| Graphic display | Yes |
| Icons | Yes |
| Custom web display | Yes |
| Geometric objects | Yes |
| Number of complex objects per screen | 80 |
| Alarm view | Yes |
| Trend view | Yes |
| User view | Yes |
| Parameter set display | Yes |
| HTML browser | Yes |
| Bar graphs | Yes |
| Sliders | Yes |
| Pointer instruments | Yes |
| Analog/digital clock | Yes |
| Number of text lists per project | 750 |
| Number of entries per text list | 750 |
| Number of graphics lists per project | 750 |
| Number of entries per graphics list | 750 |
| Number of archives per device | 50 |
| Number of entries per archive | 500 000 |
| Message archive | Yes |
| Process value archive | Yes |
| Sequential archive | Yes |
| Short-term archive | Yes |
| Memory card | Yes |
| USB memory | Yes |
| Number of roles | 50 |
| Number of function rights | 20; number of predefined function rights |
| Number of users | 200 |
| Password export/import | Yes |
| Central user administration | Yes; as of WinCC Unified V17 |
| using external storage medium | Yes; as of WinCC Unified V17 |
| S7-1200 | Yes |
| S7-1500 | Yes |
| S7-200 | Yes |
| S7-300/400 | Yes |
| Number of S7 connections | 16 |
| LOGO! | Yes; as of WinCC Unified V20 |
| Allen Bradley (DF1) | Yes |
| Mitsubishi (MC TCP/IP) | Yes |
| Mitsubishi (FX) | Yes |
| OMRON (FINS TCP) | Yes |
| Software Controller/Open Controller | Yes |
| Backup/Restore manually | Yes |
| Backup/Restore automatically | Yes |
| Simulation | Yes |
| Device switchover | Yes |
| Peripherals | Printer, barcode reader |
| Printer | Yes |
| SIMATIC HMI SD memory card: Secure Digital memory card | Yes |
| SIMATIC IPC USB Flashdrive (USB stick) | Yes |
| SIMATIC HMI USB stick | Yes |
| Aluminum | Yes |
| Width of the housing front | 398 mm |
| Height of housing front | 257 mm |
| Mounting cutout, width | 382 mm |
| Mounting cutout, height | 241 mm |
| mounting depth | 73 mm |
| EMV | For use in hazardous locations |
| For use in hazardous locations | Maritime application |
| okai | tion Society) |
| last modified: | 6/17/2026 |