Especificaciones técnicas
Protección y seguridad
| Reverse polarity protection | Yes |
|---|---|
| Short-circuit protection | Yes; Electronic |
| Short-circuit to ground | Yes; module-wise |
| Short-circuit to L+ | Yes; module-wise |
| Isolation tested with | 707 V DC (type test) |
| Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
Datos eléctricos
| Current consumption, max. | 30 mA; without load |
|---|---|
| Power loss, typ. | 1W |
| Current-sourcing | Yes |
| Limitation of inductive shutdown voltage to | Typ. L+ (-50 V) |
| for signal "0" residual current, max. | 0.1 mA |
| Current per channel, max. | 0.5 A |
| Current per module, max. | 8 A; see Equipment Manual "Derating curve" |
| Monitoring the supply voltage | Yes |
| Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Montaje y material
| Color code for module-specific color-coded label | CC00 |
|---|
Condiciones ambientales
| Installation altitude above sea level, max. | 5 000 m |
|---|
Certificados y homologaciones
| China RoHS | CCC-Ex |
|---|
Otras características
| Product type designation | DQ 16x24VDC/0.5A ST |
|---|---|
| based on | 6ES7132-6BH01-0BA0 |
| usable BaseUnits | BU type A0 |
| I&M data | Yes; I&M0 to I&M3 |
| STEP 7 TIA Portal configurable/integrated from version | see entry ID: 109746275 |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Address space per module, max. | 2 byte; + 2 bytes for QI information |
| Automatic encoding | Yes |
| Mechanical coding element | Yes |
| Type of mechanical coding element | Type A |
| 1-wire connection | BU type A0 |
| 2-wire connection | BU type A0 with AUX terminals or potential distributor module |
| 3-wire connection | BU type A0 with AUX terminals or potential distributor module |
| Type of digital output | Source output (PNP, current-sourcing) |
| Number of digital outputs | 16 |
| Digital outputs, parameterizable | Yes |
| output type acc. to IEC 61131, type 0.5 | Yes |
| Response threshold, typ. | 1 A; 0.7 to 1.3 A |
| Open-circuit detection | Yes |
| Controlling a digital input | Yes |
| lower limit | 48 Ω |
| upper limit | 12 kΩ |
| for signal "1" rated value | 0.5 A |
| for signal "1" permissible range, max. | 0.5 A |
| "0" to "1", typ. | 50 µs |
| "1" to "0", typ. | 100 µs |
| for redundant control of a load | Yes |
| up to 40 °C, max. | 8A |
| up to 50 °C, max. | 6A |
| up to 60 °C, max. | 4A |
| up to 30 °C, max. | 8A |
| shielded, max. | 1 000 m |
| unshielded, max. | 600 m |
| Diagnostics function | Yes |
| Substitute values connectable | Yes |
| Diagnostic alarm | Yes |
| Wire break | Yes; module-wise |
| Group error | Yes |
| Channel status display | Yes; green LED |
| for module diagnostics | Yes; green/red DIAG LED |
| between the channels and backplane bus | Yes |
| horizontal installation, min. | -40 °C; = Tmin (incl. condensation/frost) |
| vertical installation, min. | -40 °C; = Tmin |
| vertical installation, max. | 50 °C; = Tmax |
| 2-38, max. | condensation conditions) |
| Resistant to commercially available coolants and | Yes; Incl. diesel and oil droplets in the air |
| 60721-3-3 | Class 3B3 on request |
| to EN 60721-3-3 | 0AA0) |
| 60721-3-6 | request |
| to EN 60721-3-6 | 0AA0) |
| conditions acc. to EN 60721, EN 60654-4 and | during operation! |
| Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
| Qualification and Performance of Electrical Insulating | Yes; Conformal coating, Class A |
| Width | 15 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Weight, approx. | 30 g |
| EMV | For use in hazardous locations |
| last modified: | 3/10/2026 |