Especificaciones técnicas
Protección y seguridad
| Product equipment of circuit breaker for motor protection | Yes |
|---|---|
| response value current of instantaneous short-circuit trip unit | 520 A |
| product function short circuit protection | Yes |
| design of the short-circuit trip | magnetic |
| device type according to ISO 13849-1 | 3 |
| overdimensioning according to ISO 13849-2 necessary | Yes |
| safety device type according to IEC 61508-2 | Type A |
| protection class IP on the front according to IEC 60529 | IP20 |
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front |
Datos eléctricos
| product extension auxiliary switch | Yes |
|---|---|
| type of calculation of power loss current-dependent | quadratic |
| insulation voltage with degree of pollution 3 at AC rated value | 1 000 V |
| surge voltage resistance rated value | 8 kV |
| continuous current rated value | 40 A |
| number of poles for main current circuit | 3 |
| type of voltage for main current circuit | AC |
| operational current rated value | 40 A |
| type of voltage for auxiliary and control circuit | AC/DC |
| for main current circuit | screw-type terminals |
| arrangement of electrical connectors for main current | Top and bottom |
Conexión y cableado
| size of contactor can be combined company-specific | S3 |
|---|---|
| AWG number as coded connectable conductor cross | 10 ... 2 |
| for main contacts for ring cable lug | 4.5 ... 6 N·m |
| outer diameter of the usable ring cable lug maximum | 19 mm |
| for main contacts with screw-type terminals | 4.5 ... 6 N·m |
Condiciones ambientales
| installation altitude at height above sea level maximum | 2 000 m |
|---|
Prestaciones y durabilidad
| B10 value with high demand rate according to SN 31920 | 5 000 |
|---|
Otras características
| product brand name | SIRIUS |
|---|---|
| design of the product | For starter combinations |
| product type designation | 3RV2 |
| size of the circuit-breaker | S3 |
| product function disconnector functionality | Yes |
| shock resistance according to IEC 60068-2-27 | 25 g / 11 ms Sinus |
| electrical endurance (operating cycles) typical | 25 000 |
| Net Weight | 2.175 kg |
| relative humidity during operation | 10 ... 95 % |
| operating frequency rated value | 50 ... 60 Hz |
| number of NC contacts for auxiliary contacts | 0 |
| number of NO contacts for auxiliary contacts | 0 |
| number of CO contacts for auxiliary contacts | 0 |
| mounting position | any |
| Mounting method of circuit breaker for Transformer | Yes |
| height | 165 mm |
| width | 70 mm |
| depth | 176 mm |
| forwards | 0 mm |
| backwards | 0 mm |
| upwards | 150 mm |
| downwards | 150 mm |
| solid | 2x (2.5 ... 16 mm²) |
| solid or stranded | 2x (2,5 ... 50 mm²), 1x (10 ... 70 mm²) |
| finely stranded with core end processing | 2x (2.5 ... 35 mm²), 1x (2.5 ... 50 mm²) |
| finely stranded without core end processing | 2x (10 ... 35 mm²), 1x (10 ... 50 mm²) |
| product function suitable for safety function | Yes |
| safety-related switching OFF | Yes |
| service life maximum | 10 a |
| test wear-related service life necessary | Yes |
| failure rate [FIT] with low demand rate according to SN | 50 FIT |
| display version for switching status | Handle |
| ate | ates/Test Report |
| other | Railway |
| 1/L1 | 3/L2 |
| last modified: | 5/5/2026 |