Especificaciones técnicas
Protección y seguridad
| Product equipment of circuit breaker for motor protection | Yes |
|---|---|
| response value current of instantaneous short-circuit trip unit | 845 A |
| product function short circuit protection | Yes |
| design of the short-circuit trip | magnetic |
| device type according to ISO 13849-1 | 3 |
| overdimensioning according to ISO 13849-2 necessary | Yes |
| safety device type according to IEC 61508-2 | Type A |
| protection class IP on the front according to IEC 60529 | IP20 |
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front |
Datos eléctricos
| product extension auxiliary switch | Yes |
|---|---|
| type of calculation of power loss current-dependent | quadratic |
| insulation voltage with degree of pollution 3 at AC rated value | 690 V |
| surge voltage resistance rated value | 6 kV |
| continuous current rated value | 59 A |
| number of poles for main current circuit | 3 |
| type of voltage for main current circuit | AC |
| operational current rated value | 59 A |
| type of voltage for auxiliary and control circuit | AC/DC |
| for main current circuit | screw-type terminals |
| arrangement of electrical connectors for main current | Top and bottom |
Conexión y cableado
| size of contactor can be combined company-specific | S2 |
|---|---|
| for AWG cables for main contacts | 2x (18 ... 2), 1x (18 ... 1) |
| AWG number as coded connectable conductor cross | 18 ... 1 |
| for main contacts with screw-type terminals | 3 ... 4.5 N·m |
Condiciones ambientales
| installation altitude at height above sea level maximum | 2 000 m |
|---|
Prestaciones y durabilidad
| B10 value with high demand rate according to SN 31920 | 5 000 |
|---|
Otras características
| product brand name | SIRIUS |
|---|---|
| design of the product | For starter combinations |
| product type designation | 3RV2 |
| size of the circuit-breaker | S2 |
| product function disconnector functionality | Yes |
| shock resistance according to IEC 60068-2-27 | 25 g / 11 ms Sinus |
| electrical endurance (operating cycles) typical | 20 000 |
| Net Weight | 1.169 kg |
| relative humidity during operation | 10 ... 95 % |
| operating frequency rated value | 50 ... 60 Hz |
| number of NC contacts for auxiliary contacts | 0 |
| number of NO contacts for auxiliary contacts | 0 |
| number of CO contacts for auxiliary contacts | 0 |
| trip class | CLASS 10 |
| mounting position | any |
| Mounting method of circuit breaker for Transformer | Yes |
| height | 140 mm |
| width | 55 mm |
| depth | 149 mm |
| forwards | 0 mm |
| backwards | 0 mm |
| upwards | 50 mm |
| downwards | 50 mm |
| solid or stranded | 2x (1 ... 35 mm²), 1x (1 ... 50 mm²) |
| finely stranded with core end processing | 2x (1 ... 25 mm²), 1x (1 ... 35 mm²) |
| design of screwdriver shaft | Diameter 5 to 6 mm |
| size of the screwdriver tip | Pozidriv size 2 |
| for main contacts | M6 |
| product function suitable for safety function | Yes |
| safety-related switching OFF | Yes |
| service life maximum | 10 a |
| test wear-related service life necessary | Yes |
| failure rate [FIT] with low demand rate according to SN | 50 FIT |
| display version for switching status | Handle |
| ate | ates/Test Report |
| other | Railway |
| 1/L1 | 3/L2 |
| last modified: | 5/5/2026 |