Especificaciones técnicas
Protección y seguridad
| design of the miniature circuit breaker for short-circuit protection | C characteristic: 10 A; 0.4 kA |
|---|---|
| for short-circuit protection of the main circuit with type of | gG: 100 A (690 V, 50 kA) |
| for short-circuit protection of the auxiliary switch required | gG: 10 A (690 V, 1 kA) |
| protection class IP on the front according to IEC 60529 | IP20 |
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front |
Datos eléctricos
| without load current share typical | 2.5 W |
|---|---|
| type of calculation of power loss current-dependent | quadratic |
| maximum permissible voltage for protective separation between | 400 V |
| number of poles for main current circuit | 3 |
| operational current at AC-6b at 690 V at ambient temperature | 47.6 A |
| type of voltage | AC |
| type of voltage of the control supply voltage | AC |
| apparent pick-up power of magnet coil at AC | 77 VA |
| inductive power factor with closing power of the coil | 0.82 |
| apparent holding power of magnet coil at AC | 9.8 VA |
| inductive power factor with the holding power of the coil | 0.25 |
| operational current of auxiliary contacts at AC-12 maximum | 10 A |
| for main current circuit | screw-type terminals |
Conexión y cableado
| size of contactor | S0 |
|---|---|
| for AWG cables for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14), 2x 12 |
| AWG number as coded connectable conductor cross | 10 ... 4 |
Condiciones ambientales
| installation altitude at height above sea level maximum | 2 000 m |
|---|
Certificados y homologaciones
| UL File Number (CCN) | E31519 (NLDX, NLDX7) |
|---|
Otras características
| product brand name | SIRIUS |
|---|---|
| product type designation | 3RT26 |
| electrical endurance (operating cycles) | 150 000 |
| Net Weight | 0.659 kg |
| relative humidity minimum | 10 % |
| relative humidity at 55 °C according to IEC 60068-2-30 | 95 % |
| number of NO contacts for main contacts | 3 |
| number of NC contacts for main contacts | 0 |
| 1 rated value | 50 Hz |
| arcing time | 10 ms |
| control version of the switch operating mechanism | Standard A1 - A2 |
| number of NC contacts for auxiliary contacts | 2 |
| attachable | 0 |
| instantaneous contact | 2 |
| number of NO contacts for auxiliary contacts | 1 |
| contact reliability of auxiliary contacts | 0.00000001 |
| contact rating of auxiliary contacts according to UL | A600 / Q600 |
| height | 150 mm |
| width | 45 mm |
| depth | 155 mm |
| for grounded parts at the side | 10 mm |
| for auxiliary and control circuit | screw-type terminals |
| solid | 1x (2.5 ... 25 mm²) |
| stranded | 2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²) |
| solid or stranded | 1x (2,5 ... 25 mm²) |
| finely stranded with core end processing | 1x (2.5 ... 16 mm²) |
| other | Dangerous goods |