Especificaciones técnicas
Protección y seguridad
| design of the electrical isolation | galvanic isolation |
|---|---|
| protection class IP on the front according to IEC 60529 | IP20 |
Datos eléctricos
| power loss [W] maximum | 1.5 W |
|---|---|
| power loss [V·A] maximum | 3 VA |
| type of voltage of the operating voltage | AC/DC |
| surge voltage resistance rated value | 6 kV |
| thermal current of the switching element with contacts | 5A |
| current monitoring | Yes |
| overcurrent detection 1 phase | Yes |
| undercurrent detection 1 phase | Yes |
| overcurrent detection DC | Yes |
| undercurrent detection DC | Yes |
| current window recognition DC | Yes |
| control supply voltage at DC rated value | 24 ... 240 V |
| type of voltage of the supply voltage | AC/DC |
| supply voltage 1 at DC | 24 ... 240 V |
| type of current for monitoring | AC/DC |
| measurable current | 0.05 ... 10 A |
| buffering time in the event of power failure minimum | 10 ms |
| number of poles for main current circuit | 1 |
| operating voltage rated value | 24 ... 240 V |
| operational current at 17 V minimum | 5A |
| continuous current of the DIAZED fuse link of the output | 6A |
| between the voltage supply and other circuits | Yes |
| for main current circuit | screw-type terminals |
Medición y rango
| relative metering precision | 20 % |
|---|
Conexión y cableado
| operating frequency with 3RT2 contactor maximum | 5 000 1/h |
|---|---|
| product component removable terminal for main circuit | Yes |
| product component removable terminal for auxiliary and | Yes |
| for AWG cables solid | 1x (20 ... 12), 2x (20 ... 14) |
| tightening torque with screw-type terminals | 0.6 ... 0.8 N·m |
Condiciones ambientales
| installation altitude at height above sea level maximum | 2 000 m |
|---|
Otras características
| product brand name | SIRIUS |
|---|---|
| product type designation | 3UG5 |
| product function | Current monitoring relay |
| degree of pollution | 3 |
| shock resistance according to IEC 60068-2-27 | sinusoidal half-wave 15 g / 11 ms |
| mechanical service life (operating cycles) typical | 10 000 000 |
| Net Weight | 0.149 kg |
| auto-RESET | Yes |
| initial value | 0.85 |
| full-scale value | 1.1 |
| when starting | 0.5 ... 30 s |
| internal resistance of the measuring circuit | 5 mΩ |
| number of NC contacts delayed switching | 0 |
| number of NO contacts delayed switching | 0 |
| delayed switching | 1 |
| due to burst according to IEC 61000-4-4 | 2 kV |
| due to conductor-earth surge according to IEC 61000-4-5 | 2 kV |
| due to conductor-conductor surge according to IEC | 1 kV |
| field-based interference according to IEC 61000-4-3 | 10 V/m |
| electrostatic discharge according to IEC 61000-4-2 | 6 kV contact discharge / 8 kV air discharge |
| between input and output | Yes |
| type of electrical connection | screw terminal |
| for auxiliary and control circuit | screw-type terminals |
| solid | 1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²) |
| finely stranded with core end processing | 1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²) |
| stranded | 20 ... 12 |
| mounting position | any |
| fastening method | screw and snap-on mounting |
| height | 100 mm |
| width | 22.5 mm |
| depth | 90 mm |
| forwards | 0 mm |
| backwards | 0 mm |
| upwards | 0 mm |
| downwards | 0 mm |
| last modified: | 6/30/2026 |