Especificaciones técnicas
Protección y seguridad
| protection class IP on the front according to IEC 60529 | IP20 |
|---|
Datos eléctricos
| power loss [W] maximum | 1.5 W |
|---|---|
| power loss [V·A] maximum | 3 VA |
| for overvoltage category III according to IEC 60664 with | 300 V |
| surge voltage resistance rated value | 6 kV |
| thermal current of the switching element with contacts | 5A |
| control supply voltage at DC rated value | 24 ... 240 V |
| buffering time in the event of power failure minimum | 20 ms |
| operational current at 17 V minimum | 5 mA |
| continuous current of the DIAZED fuse link of the output | 6A |
| between the voltage supply and other circuits | Yes |
Medición y rango
| relative metering precision | 20 % |
|---|
Conexión y cableado
| operating frequency with 3RT2 contactor maximum | 5 000 1/h |
|---|---|
| product component removable terminal for auxiliary and | Yes |
| for AWG cables solid | 1x (20 ... 12) |
| for AWG cables stranded | 20 ... 12 |
Condiciones ambientales
| installation altitude at height above sea level maximum | 2 000 m |
|---|
Otras características
| product brand name | SIRIUS |
|---|---|
| design of the product | level monitoring, externally supplied with auxiliary voltage |
| product type designation | 3UG5 |
| product function | analog setting level monitoring relay |
| display version LED | Yes |
| degree of pollution | 3 |
| shock resistance according to IEC 60068-2-27 | sinusoidal half-wave 15 g / 11 ms |
| mechanical service life (operating cycles) typical | 10 000 000 |
| relative repeat accuracy | 1% |
| Net Weight | 0.151 kg |
| outlet monitoring adjustable | Yes |
| adjustable responsiveness | Yes |
| inlet monitoring adjustable | Yes |
| initial value | 0.85 |
| full-scale value | 1.1 |
| adjustable operating delay time | 0.5 ... 30 s |
| response time maximum | 500 ms |
| physical measuring principle | conductive |
| temperature drift per °C | 1 %/°C |
| for auxiliary contacts | 1 |
| delayed switching | 1 |
| number of inputs | 2 |
| due to burst according to IEC 61000-4-4 | 2 kV |
| due to conductor-earth surge according to IEC 61000-4-5 | 2 kV |
| due to conductor-conductor surge according to IEC | 1 kV |
| field-based interference according to IEC 61000-4-3 | 10 V/m |
| electrostatic discharge according to IEC 61000-4-2 | 6 kV contact discharge / 8 kV air discharge |
| between input and output | Yes |
| type of electrical connection | spring-loaded terminal (push-in) |
| solid | 1x (0.5 ... 4 mm²) |
| finely stranded with core end processing | 1x (0.5 ... 2.5 mm²) |
| finely stranded without core end processing | 0.5 ... 4 mm² |
| stranded | 20 ... 12 |
| mounting position | any |
| fastening method | screw and snap-on mounting |
| height | 100 mm |
| width | 22.5 mm |
| depth | 90 mm |
| forwards | 0 mm |
| backwards | 0 mm |
| upwards | 0 mm |
| downwards | 0 mm |
| MAX | 11 |
| last modified: | 6/30/2026 |