Especificaciones técnicas
Protección y seguridad
| design of the fuse link for short-circuit protection of the auxiliary | fuse gL/gG: 6 A |
|---|---|
| performance level (PL) according to ISO 13849-1 | PL c |
| category according to ISO 13849-1 | 1 |
| device type according to ISO 13849-1 | 1 |
| Safety Integrity Level (SIL) according to IEC 61508 | SIL 2 |
| safety device type according to IEC 61508-2 | Type A |
| PFHD with high demand rate according to IEC 61508 | 6E-7 1/h |
| PFDavg with low demand rate according to IEC 61508 | 0.002 |
| hardware fault tolerance according to IEC 61508 | 0 |
| T1 value of service life according to IEC 61508 | 20 a |
Seguridad funcional
| MTTFd | 470 a |
|---|
Datos eléctricos
| consumed active power | 2.3 W |
|---|---|
| insulation voltage for overvoltage category III according to IEC | 300 V |
| surge voltage resistance rated value | 4 kV |
| thermal current of the switching element with contacts | 5A |
| control supply voltage at DC rated value | 24 ... 240 V |
| control supply voltage at DC | 24 ... 240 V |
| type of voltage | AC/DC |
| output current minimum | 10 mA |
Conexión y cableado
| product component removable terminal for auxiliary and | Yes |
|---|---|
| for AWG cables solid | 1x (20 ... 12) |
| stripped length of the cable for auxiliary and control contacts | 10 mm |
Montaje y material
| material of switching contacts | AgSnO2 + Au flash |
|---|
Condiciones ambientales
| installation altitude at height above sea level maximum | 2 000 m |
|---|
Otras características
| product brand name | SIRIUS |
|---|---|
| design of the product | fail-safe up to SIL 2/PL c |
| product type designation | 3RQ1 |
| degree of pollution | 3 |
| according to IEC 60068-2-27 | 11 g / 15 ms |
| according to IEC 60068-2-6 | 10 ... 55 Hz: 0.35 mm |
| operating frequency maximum | 360 1/h |
| switching behavior | monostable |
| mechanical service life (operating cycles) typical | 10 000 000 |
| Net Weight | 0.172 kg |
| initial value | 0.7 |
| full-scale value | 1.1 |
| OFF-delay time maximum | 60 ms |
| design of the switching function | NC contact and NO contact |
| number of NC contacts for auxiliary contacts | 2 |
| number of NO contacts for auxiliary contacts | 2 |
| number of CO contacts for auxiliary contacts | 0 |
| EMC emitted interference according to IEC 60947-1 | ambience A (industrial sector) |
| EMC immunity according to IEC 60947-1 | corresponds to degree of severity 3 |
| due to burst according to IEC 61000-4-4 | 2 kV |
| due to conductor-earth surge according to IEC 61000-4-5 | 2 kV (line to ground) |
| due to conductor-conductor surge according to IEC | 1 kV (line to line) |
| field-based interference according to IEC 61000-4-3 | 10 V/m |
| electrostatic discharge according to IEC 61000-4-2 | 4 kV contact discharging, 8 kV air discharging |
| product component LED | Yes |
| positively driven operation according to IEC 60947-5-1 | Yes |
| safety-related switching OFF | Yes |
| safe state | safe shutdown |
| test wear-related service life necessary | Yes |
| stop category according to IEC 60204-1 | 0 |
| according to IEC 62061 | SIL 2 |
| Safe failure fraction (SFF) | 85 % |
| type of electrical connection | spring-loaded terminal (push-in) |
| wire length at DC maximum | 2 000 m |
| solid | 1x (0.5 ... 4 mm²) |
| finely stranded with core end processing | 1x (0.5 ... 2.5 mm²) |
| finely stranded with core end processing maximum | 2.5 mm² |
| finely stranded without core end processing minimum | 0.5 mm² |
| stranded | 12 ... 20 |
| mounting position | any |
| fastening method | screw and snap-on mounting onto 35 mm DIN rail |
| height | 100 mm |
| width | 22.5 mm |
| depth | 90 mm |
| relative humidity during operation | 10 ... 95 % |
| EMV | Maritime application |
| other | Railway |
| last modified: | 5/16/2026 |