Especificaciones técnicas
Protección y seguridad
| Isolation tested with | 2 545 V DC/2 s (routine test) |
|---|
Datos eléctricos
| Current consumption (rated value) | 10 mA |
|---|---|
| Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Entradas/Salidas y comunicación
| suitable for operation on PROFINET R1 IMs | Yes |
|---|---|
| PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
| PROFINET from GSD version/GSD revision | GSDML V2.3 |
Detección y sensórica
| 2-wire sensor | Yes |
|---|
Montaje y material
| Color code for module-specific color-coded label | CC41 |
|---|
Condiciones ambientales
| Installation altitude above sea level, max. | 2 000 m; On request: Installation altitudes greater than 2 000 m |
|---|
Otras características
| Product type designation | DI 4x120...230VAC ST |
|---|---|
| HW functional status | from FS04 |
| Firmware version | V0.0 |
| usable BaseUnits | BU type B1 |
| I&M data | Yes; I&M0 to I&M3 |
| STEP 7 TIA Portal configurable/integrated from version | V14 |
| STEP 7 configurable/integrated from version | V5.5 SP3 |
| Rated value (AC) | 230 V |
| permissible range, upper limit (AC) | 264 V |
| Number of outputs | 4 |
| up to 60 °C, max. | 10 A |
| Address space per module, max. | 1 byte; + 1 byte for QI information |
| Automatic encoding | Yes |
| Mechanical coding element | Yes |
| Type of mechanical coding element | type C |
| 1-wire connection | BU type B1 |
| 2-wire connection | BU type B1 |
| 3-wire connection | BU type B1 |
| 4-wire connection | BU type B1 + potential distributor module |
| Number of digital inputs | 4 |
| Digital inputs, parameterizable | Yes |
| Sourcing/sinking input | P-reading |
| for signal "0" | 0V AC to 40V AC |
| for signal "1" | 74 V AC to 264 V AC |
| for signal "1", typ. | 10.8 mA |
| shielded, max. | 1 000 m |
| unshielded, max. | 600 m |
| Channel status display | Yes; green LED |
| for module diagnostics | Yes; green/red DIAG LED |
| between the channels and backplane bus | Yes |
| horizontal installation, min. | -30 °C |
| horizontal installation, max. | 60 °C |
| vertical installation, min. | -30 °C |
| vertical installation, max. | 50 °C |
| dew point, min. | -60 °C; suitable for dry room applications |
| Width | 20 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Weight, approx. | 36 g |
| last modified: | 2/4/2026 |