Especificaciones técnicas
Protección y seguridad
| Reverse polarity protection | Yes |
|---|---|
| Short-circuit protection | Yes |
| short-circuit | Yes; channel by channel |
| Isolation tested with | 707 V DC (type test) |
Datos eléctricos
| Current consumption (rated value) | 20 mA |
|---|---|
| Current consumption, max. | 39 mA |
| Output voltage, min. | 19.2 V |
| Output current per channel, max. | 700 mA |
| Output current per module, max. | 700 mA |
| Power loss, typ. | 1.5 W; 24 V, 8 inputs supplied via encoder supply |
| Pulse extension | Yes; Pulse duration from 4 µs |
| permissible quiescent current (2-wire sensor), max. | 1.5 mA |
| Monitoring the supply voltage | Yes |
| Monitoring of encoder power supply | Yes; channel by channel |
| Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Entradas/Salidas y comunicación
| PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
|---|---|
| PROFINET from GSD version/GSD revision | GSDML V2.3 |
Detección y sensórica
| 2-wire sensor | Yes |
|---|
Montaje y material
| Color code for module-specific color-coded label | CC01 |
|---|
Condiciones ambientales
| Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
|---|
Otras características
| Product type designation | DI 8x24 V DC HF |
|---|---|
| HW functional status | From FS07 |
| FW update possible | Yes |
| usable BaseUnits | BU type A0 |
| I&M data | Yes; I&M0 to I&M3 |
| Isochronous mode | Yes |
| STEP 7 TIA Portal configurable/integrated from version | V13 SP1 / - |
| STEP 7 configurable/integrated from version | V5.5 / - |
| PCS 7 configurable/integrated from version | V8.1 SP1 |
| PCS neo can be configured/integrated from version | from V1.0.0 |
| MSI | Yes |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Number of outputs | 8 |
| 24 V | Yes |
| Inputs | 1 byte; + 1 byte for QI information |
| Automatic encoding | Yes |
| Mechanical coding element | Yes |
| Type of mechanical coding element | Type A |
| Number of configurable submodules, max. | 4 |
| 1-wire connection | BU type A0 |
| 2-wire connection | BU type A0 |
| 3-wire connection | BU type A0 with AUX terminals or potential distributor module |
| 4-wire connection | BU type A0 + Potential distributor module |
| Number of digital inputs | 8 |
| Digital inputs, parameterizable | Yes |
| Sourcing/sinking input | P-reading |
| Length | 2 s; 50 ms, 100 ms, 200 ms, 500 ms, 1 s, 2 s |
| Edge evaluation | Yes; rising edge, falling edge, edge change |
| for signal "0" | -30 to +5 V |
| for signal "1" | +11 to +30V |
| for signal "1", typ. | 2.5 mA |
| shielded, max. | 1 000 m |
| unshielded, max. | 600 m |
| Filtering and processing time (TCI), min. | 420 µs |
| Bus cycle time (TDP), min. | 500 µs |
| Jitter, max. | 8 µs |
| Diagnostics function | Yes |
| Diagnostic alarm | Yes; channel by channel |
| Hardware interrupt | Yes; Parameterizable, channels 0 to 7 |
| Diagnostic information readable | Yes |
| Parameterizable | Yes |
| Channel status display | Yes; green LED |
| for channel diagnostics | Yes; red LED |
| for module diagnostics | Yes; green/red DIAG LED |
| between the channels and backplane bus | Yes |
| horizontal installation, min. | -30 °C; < 0 °C as of FS07 |
| horizontal installation, max. | 60 °C |
| vertical installation, min. | -30 °C; < 0 °C as of FS07 |
| vertical installation, max. | 50 °C |
| Width | 15 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Weight, approx. | 28 g |
| other | Environment |
| last modified: | 10/23/2025 |