SITOP PSU8200/1AC/DC24V/40A/EX
Siemens

SITOP PSU8200/1AC/DC24V/40A/EX

SITOP PSU8200 Ex 24 V/40 A fuente de alimentación estabilizada entrada: 120/230 V AC, salida: 24 V DC/40 A

Medición y rango
relative control precision of the output voltage with rapid1%
relative control precision of the output voltage load step of1.9 %
relative control precision of the output voltage at load step of3.8 %
Prestaciones y durabilidad
MTBF at 40 °C838 156 h
Certificados y homologaciones
ATEXYes; ATEX (EX) II 3G Ex ec nC IIC T3 Gc
Otras características
type of the power supply network1-phase and 2-phase AC
supply voltage at ACAutomatic selection; startup starting from Ue ≥ 90/180 V
supply voltage120 V/230 V
input voltage 1 at AC85 ... 132 V
input voltage 2 at AC170 ... 264 V
operating condition of the mains bufferingat Vin = 230 V
line frequency50/60 Hz
at rated input voltage 120 V15 A
at rated input voltage 230 V9A
current limitation of inrush current at 25 °C maximum50 A
I2t value maximum8 A²·s
fuse protection typeYes
fuse protection type in the feederRecommended miniature circuit breaker at 1-phase operation: 16 A
voltage curve at outputControlled, isolated DC voltage
output voltage at DC rated value24 V
at output 1 at DC rated value24 V
output voltage adjustableYes; via potentiometer
adjustable output voltage24 ... 28 V; max. 960 W
relative overall tolerance of the voltage3%
on slow fluctuation of input voltage0.1 %
on slow fluctuation of ohm loading0.1 %
maximum100 mV
typical50 mV
type of signal at outputRelay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
behavior of the output voltage when switching onOvershoot of Vout approx. 3 %
response delay maximum1.5 s
rated value40 A
rated range0 ... 40 A; +60 ... +70 °C: Derating 3%/K
supplied active power typical960 W
on short-circuiting during the start-up typical120 A
at short-circuit during operation typical120 A
on short-circuiting during the start-up25 ms
at short-circuit during operation25 ms
efficiency in percent92 %
at rated output voltage for rated value of the output82 W
during no-load operation maximum6.8 W
load step 50 to 100% typical2 ms
load step 100 to 50% typical2 ms
load step 10 to 90% typical1 ms
load step 90 to 10% typical1 ms
design of the overvoltage protection< 32 V
property of the output short-circuit proofYes
in normal operation250% Iout rated up to 25 ms, 150% Iout rated up to 5 s/min
galvanic isolation between input and outputYes
galvanic isolationOutput voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection classClass I
protection class IPIP20
for emitted interferenceEN 55022 Class B
for interference immunityEN 61000-6-2
CE markingYes
UL approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
UKCA markingYes
Regulatory Compliance Mark (RCM)Yes
BISYes; R-41183539
CB-certificateYes
IECExYes; IECEx Ex ec nC IIC T3 Gc
ULhazloc approvalYes
UKEXYes
CCC for hazardous zone according to GB standardYes
Det Norske Veritas (DNV)Yes
total2 152 kg
during manufacturing74 kg
during operation2 076.5 kg
during transport-40 ... +85 °C
during storage-40 ... +85 °C
type of electrical connectionscrew terminal
at output+, -: 2 screw terminals each for 0.5 ... 10 mm²
for auxiliary contacts13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm²
width × height × depth of the enclosure145 × 145 × 150 mm
installation width × mounting height150 mm × 225 mm
top40 mm
bottom40 mm
left0 mm
right0 mm
fastening methodSnaps onto DIN rail EN 60715 35x15
DIN-rail mountingYes
housing can be lined upYes
net weight3.1 kg
electrical accessoriesBuffer module, redundancy module
mechanical accessoriesDevice identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20
IDEA4
UNSPSC15
BIS CRSMiscellaneous
last modified:5/5/2026