Especificaciones técnicas
Protección y seguridad
| intrinsic device protection | Yes |
|---|---|
| evaluation of thermistor motor protection | Yes; Type A PTC or Klixon / Thermoclick |
| type of the motor protection | Electronic, tripping in the event of thermal overload of the motor |
| design of the overvoltage protection | Varistor |
| protection class IP on the front according to IEC 60529 | IP00 |
| Safety Integrity Level (SIL) according to IEC 61508 relating | SIL 1 |
| PFHD with high demand rate according to IEC 61508 | 5E-7 1/h |
| PFDavg with low demand rate according to IEC 61508 | 0.008 |
| hardware fault tolerance according to IEC 61508 relating to | 0 |
Datos eléctricos
| starting voltage [%] | 20 ... 100 % |
|---|---|
| stopping voltage [%] | 50 %; non-adjustable |
| current limiting value [%] adjustable | 125 ... 800 % |
| breakaway voltage [%] adjustable | 40 ... 100 % |
| current unbalance limiting value [%] | 10 ... 60 % |
| for main current circuit | 100 ms |
| insulation voltage rated value | 480 V |
| impulse voltage rated value | 6 kV |
| blocking voltage of the thyristor maximum | 1 400 V |
| surge voltage resistance rated value | 6 kV |
| adjustable current limitation | Yes |
| voltage ramp | Yes |
| relative negative tolerance of the operating voltage | -15 % |
| relative positive tolerance of the operating voltage | 10 % |
| relative negative tolerance of the operating voltage at | -15 % |
| relative positive tolerance of the operating voltage at | 10 % |
| type of voltage of the control supply voltage | AC |
| relative negative tolerance of the control supply voltage at | -15 % |
| relative positive tolerance of the control supply voltage at | 10 % |
| control supply voltage frequency | 50 ... 60 Hz |
| relative negative tolerance of the control supply voltage | -10 % |
| relative positive tolerance of the control supply voltage | 10 % |
| control supply current in standby mode rated value | 100 mA |
| holding current in bypass operation rated value | 210 mA |
| inrush current by closing the bypass contacts maximum | 1A |
| inrush current peak at application of control supply voltage | 44 A |
| duration of inrush current peak at application of control supply | 1.7 ms |
Entradas/Salidas y comunicación
| PROFINET standard | Yes |
|---|---|
| PROFINET high-feature | Yes |
| EtherNet/IP | Yes |
| Modbus RTU | Yes |
| Modbus TCP | Yes |
| PROFIBUS | Yes |
Conexión y cableado
| screw terminal | Yes |
|---|---|
| removable terminal for control circuit | Yes |
| for DIN cable lug for main contacts stranded | 2x (50 ... 240 mm²) |
| for DIN cable lug for main contacts finely stranded | 2x (70 ... 240 mm²) |
| for AWG cables for control circuit solid | 1x (20 ... 12), 2x (20 ... 14) |
| for main contacts with screw-type terminals | 20 ... 35 N·m |
Condiciones ambientales
| vibration resistance | 15 mm up to 6 Hz; 2 g up to 500 Hz |
|---|---|
| installation altitude at height above sea level maximum | 5 000 m |
Certificados y homologaciones
| CE marking | Yes |
|---|---|
| UL approval | Yes |
| CSA approval | Yes |
| ATEX | Yes |
| IECEx | Yes |
| according to ATEX directive 2014/34/EU | BVS 18 ATEX F 003 X |
Otras características
| product brand name | SIRIUS |
|---|---|
| product category | Hybrid switching devices |
| product type designation | 3RW55 |
| start-up ramp time of soft starter | 0 ... 360 s |
| ramp-down time of soft starter | 0 ... 360 s |
| start torque [%] | 10 ... 100 % |
| stopping torque [%] | 10 ... 100 % |
| torque limitation [%] | 20 ... 200 % |
| breakaway time adjustable | 0 ... 2 s |
| number of parameter sets | 3 |
| accuracy class | 5 (based on IEC 61557-12) |
| HMI-High Feature | Yes |
| is supported HMI-High Feature | Yes |
| product feature integrated bypass contact system | Yes |
| number of controlled phases | 3 |
| ground-fault monitoring limiting value [%] | 10 ... 95 % |
| for control circuit | 100 ms |
| idle time adjustable | 0 ... 255 s |
| degree of pollution | 3, acc. to IEC 60947-4-2 |
| service factor | 1.15 |
| between main and auxiliary circuit | 480 V; does not apply for thermistor connection |
| shock resistance | 15 g / 11 ms, from 6 g / 11 ms with potential contact lifting |
| recovery time after overload trip adjustable | 60 ... 1 800 s |
| utilization category according to IEC 60947-4-2 | AC 53a |
| Net Weight | 70 kg |
| ramp-up (soft starting) | Yes |
| soft stopping | Yes |
| breakaway pulse | Yes |
| creep speed in both directions of rotation | Yes |
| pump stop | Yes |
| DC braking | Yes |
| motor heating | Yes |
| min/max pointer | Yes |
| trace function | Yes |
| inside-delta circuit | Yes |
| auto-RESET | Yes |
| manual RESET | Yes |
| remote reset | Yes |
| communication function | Yes |
| operating measured value display | Yes |
| event list | Yes |
| error logbook | Yes |
| via software parameterizable | Yes |
| via software configurable | Yes |
| firmware update | Yes |
| torque control | Yes |
| combined braking | Yes |
| analog output | Yes; 4 ... 20 mA (default) / 0 ... 10 V |
| programmable control inputs/outputs | Yes |
| condition monitoring | Yes |
| automatic parameterisation | Yes |
| application wizards | Yes |
| alternative stopping mode | Yes |
| emergency operation mode | Yes |
| reversing operation | Yes |
| soft starting at heavy starting conditions | Yes |
| Operating frequency 1 rated value | 50 Hz |
| Operating frequency 2 rated value | 60 Hz |
| relative negative tolerance of the operating frequency | -10 % |
| relative positive tolerance of the operating frequency | 10 % |
| minimum load [%] | 10 %; Relative to set Ie |
| number of digital inputs | 4 |
| parameterizable | 4 |
| number of digital outputs | 4 |
| number of digital outputs parameterizable | 3 |
| number of digital outputs not parameterizable | 1 |
| digital output version | 3 normally-open contacts (NO) / 1 changeover contact (CO) |
| number of analog outputs | 1 |
| fastening method | screw fixing |
| height | 764 mm |
| width | 478 mm |
| depth | 241 mm |
| forwards | 10 mm |
| backwards | 0 mm |
| upwards | 100 mm |
| downwards | 75 mm |
| width of connection bar maximum | 55 mm |
| for control circuit solid | 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²) |
| between soft starter and motor maximum | 800 m |
| for auxiliary and control contacts with screw-type | 0.8 ... 1.2 N·m |
| EMC emitted interference | acc. to IEC 60947-4-2: Class A |
| usable for Standard Faults up to 575/600 V | Type: Class J / L, max. 3000 A; Iq = 85 kA |
| usable for High Faults up to 575/600 V according to | Type: Class J / L, max. 3000 A; Iq = 100 kA |
| usable for Standard Faults at inside-delta circuit up | Type: Class J / L, max. 3000 A; Iq = 85 kA |
| usable for High Faults at inside-delta circuit up to | Type: Class J / L, max. 3000 A; Iq = 100 kA |
| contact rating of auxiliary contacts according to UL | R300-B300 |
| 1/L1 | 3/L2 |
| 5/L3 | A1 |
| 13 NO | 23 NO |
| DI 1 | DI 2 |
| DI 3 | DI 4 |
| 98 NO | 96 NC |
| last modified: | 9/5/2025 |