Contactor SIRIUS Innovations, 5kW, S0, resorte
Siemens

Contactor SIRIUS Innovations, 5kW, S0, resorte

SIRIUS Innovations Contactor, AC-3, 18, 5KW/400v, 1na+1nc, AC 230v 50/60hz, S0 conexión resorte

Datasheet
Contactor SIRIUS Innovations, 5kW, S0, resorte
€108,81 EUR
€294,07 EUR
3RT2028-2AL20
Plazo de entrega (días):
€108,81 EUR /cada
Total:

Especificaciones técnicas

product brand name SIRIUS
product designation Power contactor
product type designation 3RT2
size of contactor S0
auxiliary switch Yes
at AC in hot operating state 9.6 W
at AC in hot operating state per pole 3.2 W
without load current share typical 2.7 W
type of calculation of power loss current-dependent quadratic
of main circuit with degree of pollution 3 rated value 690 V
of auxiliary circuit with degree of pollution 3 rated value 690 V
of main circuit rated value 6 kV
of auxiliary circuit rated value 6 kV
maximum permissible voltage for protective separation between 400 V
at AC 8,3 g / 5 ms, 5,3 g / 10 ms
of contactor typical 10 000 000
of the contactor with added electronically optimized 5 000 000
of the contactor with added auxiliary switch block typical 10 000 000
reference code according to IEC 81346-2 Q
Substance Prohibitance (day/month/year) 10/01/2009
Net Weight 0.46 kg
installation altitude at height above sea level maximum 2 000 m
during operation -25 ... +60 °C
during storage -55 ... +80 °C
relative humidity minimum 10 %
relative humidity at 55 °C according to IEC 60068-2-30 95 %
number of poles for main current circuit 3
number of NO contacts for main contacts 3
number of NC contacts for main contacts 0
at AC-3 rated value maximum 690 V
at AC-3e rated value maximum 690 V
at AC-1 at 400 V at ambient temperature 40 °C rated 50 A
up to 690 V at ambient temperature 40 °C rated 50 A
up to 690 V at ambient temperature 60 °C rated 42 A
at 400 V rated value 38 A
at 500 V rated value 32 A
at 690 V rated value 21 A
at AC-4 at 400 V rated value 22 A
at AC-5a up to 690 V rated value 44 A
at AC-5b up to 400 V rated value 31.5 A
up to 230 V for current peak value n=20 rated value 30.8 A
up to 400 V for current peak value n=20 rated value 30.8 A
up to 500 V for current peak value n=20 rated value 30.8 A
up to 690 V for current peak value n=20 rated value 21 A
up to 230 V for current peak value n=30 rated value 20.5 A
up to 400 V for current peak value n=30 rated value 20.5 A
up to 500 V for current peak value n=30 rated value 21.4 A
up to 690 V for current peak value n=30 rated value 21 A
minimum cross-section in main circuit at maximum AC-1 rated 10 mm²
at 24 V rated value 35 A
at 60 V rated value 20 A
at 110 V rated value 4.5 A
at 220 V rated value 1A
at 440 V rated value 0.4 A
at 600 V rated value 0.25 A
at 230 V rated value 11 kW
limited to 1 s switching at zero current maximum 593 A; Use minimum cross-section acc. to AC-1 rated value
limited to 5 s switching at zero current maximum 341 A; Use minimum cross-section acc. to AC-1 rated value
limited to 10 s switching at zero current maximum 260 A; Use minimum cross-section acc. to AC-1 rated value
limited to 30 s switching at zero current maximum 199 A; Use minimum cross-section acc. to AC-1 rated value
limited to 60 s switching at zero current maximum 162 A; Use minimum cross-section acc. to AC-1 rated value
at AC-1 maximum 1 000 1/h
at AC-2 maximum 750 1/h
at AC-3 maximum 750 1/h
maximum 750 1/h
at AC-4 maximum 250 1/h
type of voltage of the control supply voltage AC
at 50 Hz rated value 230 V
at 60 Hz rated value 230 V
at 50 Hz 0.8 ... 1.1
at 60 Hz 0.85 ... 1.1
arcing time 10 ms
control version of the switch operating mechanism Standard A1 - A2
number of NC contacts for auxiliary contacts instantaneous 1
number of NO contacts for auxiliary contacts instantaneous 1
operational current at AC-12 maximum 10 A
at 48 V rated value 6A
at 125 V rated value 2A
contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
at 480 V rated value 34 A
at 110/120 V rated value 3 hp
at 200/208 V rated value 10 hp
at 220/230 V rated value 10 hp
at 460/480 V rated value 25 hp
at 575/600 V rated value 25 hp
contact rating of auxiliary contacts according to UL A600 / P600
UL File Number (CCN) E31519 (NLDX, NLDX7)
design of the miniature circuit breaker for short-circuit protection C characteristic: 10 A; 0.4 kA
for short-circuit protection of the auxiliary switch required gG: 10 A (500 V, 1 kA)
fastening method side-by-side mounting Yes
height 102 mm
width 45 mm
depth 97 mm
forwards 10 mm
upwards 10 mm
downwards 10 mm
at the side 0 mm
for main current circuit spring-loaded terminals
for auxiliary and control circuit spring-loaded terminals
at contactor for auxiliary contacts Spring-type terminals
of magnet coil Spring-type terminals
solid 2x (1 ... 10 mm²)
solid or stranded 2x (1 ... 10 mm²)
finely stranded with core end processing 2x (1 ... 6 mm²)
finely stranded without core end processing 2x (1 ... 6 mm²)
for AWG cables for main contacts 2x (18 ... 8)
stranded 1 ... 10 mm²
for AWG cables for auxiliary contacts 2x (20 ... 14)
AWG number as coded connectable conductor cross 18 ... 8
mirror contact according to IEC 60947-4-1 Yes
suitable for safety function Yes
suitability for use safety-related switching OFF Yes
service life maximum 20 a
test wear-related service life necessary Yes
with low demand rate according to SN 31920 40 %
with high demand rate according to SN 31920 73 %
B10 value with high demand rate according to SN 31920 1 000 000
failure rate [FIT] with low demand rate according to SN 100 FIT
device type according to ISO 13849-1 3
overdimensioning according to ISO 13849-2 necessary Yes
safety device type according to IEC 61508-2 Type A
protection class IP on the front according to IEC 60529 IP20
touch protection on the front according to IEC 60529 finger-safe, for vertical contact from the front
global warming potential [CO2 eq] / during manufacturing 1.9 kg
global warming potential [CO2 eq] / during operation 72.4 kg
global warming potential [CO2 eq] / after end of life -0.117 kg
global warming potential [CO2 eq] / total 74.2 kg
Maritime application other
other Railway
14 22