Especificaciones técnicas
Protección y seguridad
| Reverse polarity protection | Yes |
|---|---|
| Voltage output, short-circuit protection | Yes |
| Voltage output, short-circuit current, max. | 45 mA |
| short-circuit | Yes; channel-by-channel, only for output type "voltage" |
| Isolation tested with | 707 V DC (type test) |
| Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
Datos eléctricos
| Current consumption (rated value) | 45 mA; without load |
|---|---|
| Current consumption, max. | 90 mA; 2 channels current output 20 mA |
| Power loss, typ. | 0.9 W |
| for voltage output two-wire connection | Yes |
| for voltage output four-wire connection | Yes |
| for current output two-wire connection | Yes |
| Voltages at the outputs | 30 V |
| Voltage, relative to output range, (+/-) | 0.4 % |
| Current, relative to output range, (+/-) | 0.4 % |
| Monitoring the supply voltage | Yes |
| Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| between the channels and the power supply of the | Yes |
Montaje y material
| Color code for module-specific color-coded label | CC00 |
|---|
Condiciones ambientales
| Installation altitude above sea level, max. | 5 000 m |
|---|
Certificados y homologaciones
| China RoHS | CCC-Ex |
|---|
Otras características
| Product type designation | AQ 2xU/I HF |
|---|---|
| FW update possible | Yes |
| based on | 6ES7135-6HB00-0CA1 |
| usable BaseUnits | BU type A0, A1 |
| I&M data | Yes; I&M0 to I&M3 |
| Isochronous mode | Yes; 250 µs |
| STEP 7 TIA Portal configurable/integrated from version | see entry ID: 109746275 |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Address space per module, max. | 4 byte; + 1 byte for QI information |
| Automatic encoding | Yes |
| Mechanical coding element | Yes |
| Type of mechanical coding element | Type A |
| Number of analog outputs | 2 |
| Cycle time (all channels), min. | 750 µs |
| 0 to 10 V | Yes; 15 bit |
| 1 V to 5 V | Yes; 13 bit |
| 5 V to +5 V | Yes; 15 bit incl. sign |
| 10 V to +10 V | Yes; 16 bit incl. sign |
| 0 to 20 mA | Yes; 15 bit |
| 20 mA to +20 mA | Yes; 16 bit incl. sign |
| 4 mA to 20 mA | Yes; 14 bit |
| shielded, max. | 1 000 m; 200 m for voltage output |
| Resolution with overrange (bit including sign), max. | 16 bit |
| for resistive load | 0.05 ms |
| for capacitive load | 0.05 ms; Max. 47 nF and 20 m cable length |
| for inductive load | 0.05 ms |
| Linearity error (relative to output range), (+/-) | 0.03 % |
| Temperature error (relative to output range), (+/-) | 0.003 %/K |
| Crosstalk between the outputs, max. | -50 dB |
| Execution and activation time (TCO), min. | 500 µs |
| Bus cycle time (TDP), min. | 750 µs |
| Jitter, max. | 5 µs |
| Diagnostics function | Yes |
| Substitute values connectable | Yes |
| Diagnostic alarm | Yes |
| Wire break | Yes; channel-by-channel, only for output type "current" |
| Group error | Yes |
| Overflow/Underflow | Yes; channel by channel |
| Channel status display | Yes; green LED |
| for channel diagnostics | Yes; red LED |
| for module diagnostics | Yes; green/red DIAG LED |
| between the channels and backplane bus | Yes |
| horizontal installation, min. | -40 °C; = Tmin (incl. condensation/frost) |
| horizontal installation, max. | 70 °C; = Tmax |
| vertical installation, min. | -40 °C; = Tmin |
| vertical installation, max. | 50 °C; = Tmax |
| 2-38, max. | horizontal installation |
| Resistant to commercially available coolants and | Yes; Incl. diesel and oil droplets in the air |
| 60721-3-3 | Class 3B3 on request |
| to EN 60721-3-3 | 0AA0) |
| 60721-3-6 | request |
| to EN 60721-3-6 | 0AA0) |
| conditions acc. to EN 60721, EN 60654-4 and | during operation! |
| Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
| Qualification and Performance of Electrical Insulating | Yes; Conformal coating, Class A |
| Width | 15 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Weight, approx. | 31 g |
| EMV | For use in hazardous locations |
| last modified: | 10/23/2025 |