SIPLUS ET 200SP AI EM CT ST
Certificados y homologaciones
EAC
Siemens

SIPLUS ET 200SP AI EM CT ST

SIPLUS ET 200SP AI EM CT ST based on: 6ES7134-6PA01-0BU0 with conformal coating, -40…+70 °C, analog input module, AI Energy Meter CT ST, for 1A or 5A current transformer, suitable for BU type U0, channel diagnostics

Montaje y material
Color code for module-specific color-coded labelCC20
Condiciones ambientales
Installation altitude above sea level, max.3 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Otras características
Product type designationAI Energy Meter CT ST
FW update possibleYes
based on6ES7134-6PA01-0BU0
usable BaseUnitsBU type U0
Supported power supply systemsTT, TN, IT
Voltage measurementYes
without voltage transformerYes
with voltage transformerYes
Current measurementYes; max. 3 + neutral conductor
with current transformerYes; 1 A or 5 A current transformer
Energy measurementYes
Frequency measurementYes
Power measurementYes
Active power measurementYes
Reactive power measurementYes
Power factor measurementYes
Active factor measurementYes
Reactive power compensationYes
I&M dataYes; I&M0 to I&M3
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Cyclic measured value accessYes
Acyclic measured value accessYes
Fixed measured value setsYes
Freely definable measured value setsYes; For cyclic and acyclic measured value access
Reparameterization possible in RUNYes
Calibration possible in RUNYes
Mounting positionany
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Current consumption (rated value)12.5 mA
Current consumption, max.17 mA
Power loss, typ.1 W; 3x 5 A input current, 3x 230 V AC
Inputs256 byte
Outputs20 byte
Automatic encodingYes
Mechanical coding elementYes
Type of mechanical coding elementtype C
2-wire connectionBU type U0
presentYes
shielded, max.200 m
unshielded, max.200 m
Sampling frequency, max.2 048 kHz
Diagnostic alarmYes
Limit value alarmYes
Supply voltageYes
Hardware interrupt lostYes
Parameter assignment errorYes
Module faultYes
Channel not availableYes
Overflow/UnderflowYes
Overload currentYes
Monitoring of the supply voltage (PWR-LED)Yes
Channel status displayYes; green LED
for channel diagnosticsYes; red Fn LED
for module diagnosticsYes; green/red DIAG LED
Measuring procedure for voltage measurementTRMS
Measuring procedure for current measurementTRMS
Type of measured value acquisitionseamless
Curve shape of voltageSinusoidal or distorted
Buffering of measured variablesYes
Parameter length128 byte
Bandwidth of measured value acquisition3.2 kHz; Harmonics: 63 / 50 Hz, 52 / 60 Hz
Frequency measurement, min.40 Hz
Frequency measurement, max.70 Hz
Measurable line voltage between phase and neutral277 V
Measurable line voltage between the line480 V
Internal resistance line conductor and neutral1.5 MΩ
Power consumption per phase60 mW; 300 V AC
Impulse voltage resistance 1,2/50µs2.5 kV
Measurement category for voltage measurement inCAT II
measurable relative current (AC), min.1 %; Relative to measuring range; 1 A, 5 A
measurable relative current (AC), max.100 %; Relative to the secondary rated current 5 A
Continuous current with AC, maximum permissible5A
Apparent power consumption per phase for0.6 VA
Rated value short-time withstand current restricted100 A
Input resistance measuring range 0 to 5 A25 mΩ; At the terminal
Surge strength10 A; for 1 minute
Zero point suppression0 ... 20%, referred to the nominal current
Measured variable voltage0,2
Measured variable current0,2
Measured variable apparent power0.5
Measured variable active power0.5
Measured variable reactive power1
Measured variable power factor0.5
Measured variable active energy0.5
Measured variable reactive energy1
Measured variable neutral current0,2
Measured variable phase angle±0.5 °; not covered by IEC 61557-12
Measured variable frequency0.05; only valid for the permissible voltage measuring range
between the channels and backplane busYes
Between the channels and load voltage L+Yes; Including FE
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.70 °C; = Tmax
vertical installation, min.-40 °C; = Tmin
vertical installation, max.50 °C; = Tmax
2-38, max.horizontal installation
Resistant to commercially available coolants andYes; Incl. diesel and oil droplets in the air
60721-3-3Class 3B3 on request
to EN 60721-3-30AA0//6AG1193-6AB00-0AA0)
60721-3-6degree 3); *
to EN 60721-3-60AA0/6AG1193-6AB00-0AA0)
conditions acc. to EN 60721, EN 60654-4 andduring operation!
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical InsulatingYes; Conformal coating, Class A
Width20 mm
Height73 mm
Depth58 mm
Weight, approx.45 g
Secondary side, max.300 V
Burden power current transformer x/1A, min.As a function of cable length and cross section, see device manual
Burden power current transformer x/5A, min.As a function of cable length and cross section, see device manual
last modified:11/26/2024

Ficha técnica oficial del fabricante con todas las especificaciones.

Producto bajo pedido

Puedes pedirlo ya: te lo servimos en el plazo indicado. Selecciona la cantidad para añadirlo al carrito. Si prefieres esperar a que vuelva a haber stock inmediato, déjanos tu email abajo.

Plazo de entrega (días):

Este artículo va bajo pedido.

Avísame cuando esté disponible

Solo usaremos tu email para avisarte de este artículo.

SIPLUS ET 200SP AI EM CT ST
€515,49 EUR
€572,77 EUR
6AG1134-6PA01-7BU0
Plazo de entrega (días):
€515,49 EUR /each
Total:

Accesorios