| product brand name | SIRIUS |
|---|
| product category | Hybrid switching devices |
|---|
| product type designation | 3RW55 |
|---|
| of high feature HMI module usable | 3RW5980-0HF00 |
|---|
| of circuit breaker usable at 400 V | 3VA2216-7MN32-0AA0; Type of coordination 1, Iq = 15 kA, CLASS 10 |
|---|
| of circuit breaker usable at 500 V | 3VA2216-7MN32-0AA0; Type of coordination 1, Iq = 10 kA, CLASS 10 |
|---|
| of the gG fuse usable up to 690 V | 3NA3136-6; Type of coordination 1, Iq = 65 kA |
|---|
| of full range R fuse link for semiconductor protection | 3NE1224-0; Type of coordination 2, Iq = 65 kA |
|---|
| of back-up R fuse link for semiconductor protection | 3NE3227; Type of coordination 2, Iq = 65 kA |
|---|
| starting voltage [%] | 20 ... 100 % |
|---|
| stopping voltage [%] | 50 %; non-adjustable |
|---|
| start-up ramp time of soft starter | 0 ... 360 s |
|---|
| ramp-down time of soft starter | 0 ... 360 s |
|---|
| start torque [%] | 10 ... 100 % |
|---|
| stopping torque [%] | 10 ... 100 % |
|---|
| torque limitation [%] | 20 ... 200 % |
|---|
| current limiting value [%] adjustable | 125 ... 800 % |
|---|
| breakaway voltage [%] adjustable | 40 ... 100 % |
|---|
| breakaway time adjustable | 0 ... 2 s |
|---|
| number of parameter sets | 3 |
|---|
| accuracy class | 5 (based on IEC 61557-12) |
|---|
| CE marking | Yes |
|---|
| UL approval | Yes |
|---|
| CSA approval | Yes |
|---|
| HMI-High Feature | Yes |
|---|
| is supported HMI-High Feature | Yes |
|---|
| product feature integrated bypass contact system | Yes |
|---|
| number of controlled phases | 3 |
|---|
| current unbalance limiting value [%] | 10 ... 60 % |
|---|
| ground-fault monitoring limiting value [%] | 10 ... 95 % |
|---|
| for main current circuit | 100 ms |
|---|
| for control circuit | 100 ms |
|---|
| idle time adjustable | 0 ... 255 s |
|---|
| insulation voltage rated value | 690 V |
|---|
| degree of pollution | 3, acc. to IEC 60947-4-2 |
|---|
| impulse voltage rated value | 8 kV |
|---|
| blocking voltage of the thyristor maximum | 1 800 V |
|---|
| service factor | 1.15 |
|---|
| surge voltage resistance rated value | 8 kV |
|---|
| between main and auxiliary circuit | 690 V; does not apply for thermistor connection |
|---|
| shock resistance | 15 g / 11 ms, from 6 g / 11 ms with potential contact lifting |
|---|
| vibration resistance | 15 mm up to 6 Hz; 2 g up to 500 Hz |
|---|
| recovery time after overload trip adjustable | 60 ... 1 800 s |
|---|
| utilization category according to IEC 60947-4-2 | AC 53a |
|---|
| Net Weight | 8 kg |
|---|
| ramp-up (soft starting) | Yes |
|---|
| soft stopping | Yes |
|---|
| breakaway pulse | Yes |
|---|
| adjustable current limitation | Yes |
|---|
| creep speed in both directions of rotation | Yes |
|---|
| pump stop | Yes |
|---|
| DC braking | Yes |
|---|
| motor heating | Yes |
|---|
| min/max pointer | Yes |
|---|
| trace function | Yes |
|---|
| intrinsic device protection | Yes |
|---|
| evaluation of thermistor motor protection | Yes; Type A PTC or Klixon / Thermoclick |
|---|
| inside-delta circuit | Yes; Only up to 600 V operating voltage |
|---|
| auto-RESET | Yes |
|---|
| manual RESET | Yes |
|---|
| remote reset | Yes |
|---|
| communication function | Yes |
|---|
| operating measured value display | Yes |
|---|
| event list | Yes |
|---|
| error logbook | Yes |
|---|
| via software parameterizable | Yes |
|---|
| via software configurable | Yes |
|---|
| firmware update | Yes |
|---|
| voltage ramp | Yes |
|---|
| torque control | Yes |
|---|
| combined braking | Yes |
|---|
| analog output | Yes; 4 ... 20 mA (default) / 0 ... 10 V |
|---|
| programmable control inputs/outputs | Yes |
|---|
| condition monitoring | Yes |
|---|
| automatic parameterisation | Yes |
|---|
| application wizards | Yes |
|---|
| alternative stopping mode | Yes |
|---|
| emergency operation mode | Yes |
|---|
| reversing operation | Yes |
|---|
| soft starting at heavy starting conditions | Yes |
|---|
| at 40 °C rated value | 93 A |
|---|
| at 40 °C rated value minimum | 19 A |
|---|
| at 50 °C rated value | 82.5 A |
|---|
| at 60 °C rated value | 75.5 A |
|---|
| rated value | 200 ... 690 V |
|---|
| at inside-delta circuit rated value | 200 ... 600 V |
|---|
| relative negative tolerance of the operating voltage | -15 % |
|---|
| relative positive tolerance of the operating voltage | 10 % |
|---|
| relative negative tolerance of the operating voltage at | -15 % |
|---|
| relative positive tolerance of the operating voltage at | 10 % |
|---|
| at 230 V at 40 °C rated value | 22 kW |
|---|
| at 230 V at inside-delta circuit at 40 °C rated value | 45 kW |
|---|
| at 400 V at 40 °C rated value | 45 kW |
|---|
| at 400 V at inside-delta circuit at 40 °C rated value | 90 kW |
|---|
| at 500 V at 40 °C rated value | 55 kW |
|---|
| at 500 V at inside-delta circuit at 40 °C rated value | 110 kW |
|---|
| at 690 V at 40 °C rated value | 90 kW |
|---|
| Operating frequency 1 rated value | 50 Hz |
|---|
| Operating frequency 2 rated value | 60 Hz |
|---|
| relative negative tolerance of the operating frequency | -10 % |
|---|
| relative positive tolerance of the operating frequency | 10 % |
|---|
| minimum load [%] | 10 %; Relative to set Ie |
|---|
| at 40 °C after startup | 28 W |
|---|
| at 50 °C after startup | 25 W |
|---|
| at 60 °C after startup | 23 W |
|---|
| at 40 °C during startup | 1 258 W |
|---|
| at 50 °C during startup | 1 065 W |
|---|
| at 60 °C during startup | 948 W |
|---|
| type of the motor protection | Electronic, tripping in the event of thermal overload of the motor |
|---|
| type of voltage of the control supply voltage | AC |
|---|
| at 50 Hz | 110 ... 250 V |
|---|
| at 60 Hz | 110 ... 250 V |
|---|
| control supply voltage frequency | 50 ... 60 Hz |
|---|
| control supply current in standby mode rated value | 100 mA |
|---|
| holding current in bypass operation rated value | 180 mA |
|---|
| inrush current by closing the bypass contacts maximum | 0.8 A |
|---|
| design of the overvoltage protection | Varistor |
|---|
| number of digital inputs | 4 |
|---|
| parameterizable | 4 |
|---|
| number of digital outputs | 4 |
|---|
| number of digital outputs parameterizable | 3 |
|---|
| number of digital outputs not parameterizable | 1 |
|---|
| digital output version | 3 normally-open contacts (NO) / 1 changeover contact (CO) |
|---|
| number of analog outputs | 1 |
|---|
| at AC-15 at 250 V rated value | 3A |
|---|
| at DC-13 at 24 V rated value | 1A |
|---|
| fastening method | screw fixing |
|---|
| height | 306 mm |
|---|
| width | 185 mm |
|---|
| depth | 203 mm |
|---|
| forwards | 10 mm |
|---|
| backwards | 0 mm |
|---|
| upwards | 100 mm |
|---|
| downwards | 75 mm |
|---|
| at the side | 5 mm |
|---|
| width of connection bar maximum | 25 mm |
|---|
| with conductor cross-section = 0.5 mm² maximum | 50 m |
|---|
| with conductor cross-section = 1.5 mm² maximum | 150 m |
|---|
| with conductor cross-section = 2.5 mm² maximum | 250 m |
|---|
| using the front clamping point solid | 1x (2.5 ... 16 mm²) |
|---|
| using the front clamping point stranded | 1x (10 ... 70 mm²) |
|---|
| using the back clamping point solid | 1x (2.5 ... 16 mm²) |
|---|
| using both clamping points solid | 2x (2.5 ... 16 mm²) |
|---|
| using both clamping points stranded | 2x (6 ... 16 mm²), 2x (10 ... 50 mm²) |
|---|
| using the back clamping point finely stranded with core | 1x (2.5 ... 50 mm²) |
|---|
| using the back clamping point stranded | 1x (10 ... 70 mm²) |
|---|
| for control circuit solid | 2x (0.25 ... 1.5 mm²) |
|---|
| between soft starter and motor maximum | 800 m |
|---|
| at the digital inputs at DC maximum | 1 000 m |
|---|
| for auxiliary and control contacts with screw-type | 0.8 ... 1.2 N·m |
|---|
| during storage and transport | -40 ... +80 °C |
|---|
| during transport according to IEC 60721 | 2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m) |
|---|
| EMC emitted interference | acc. to IEC 60947-4-2: Class A, Class B on request |
|---|
| usable for Standard Faults up to 575/600 V | Type: Class RK5 / K5, max. 300 A; Iq = 10 kA |
|---|
| usable for High Faults up to 575/600 V according to | Type: Class J / L, max. 250 A; Iq = 100 kA |
|---|
| usable for Standard Faults at inside-delta circuit up | Type: Class RK5 / K5, max. 300 A; Iq = 10 kA |
|---|
| usable for High Faults at inside-delta circuit up to | Type: Class J / L, max. 250 A; Iq = 100 kA |
|---|
| at 200/208 V at 50 °C rated value | 25 hp |
|---|
| at 220/230 V at 50 °C rated value | 30 hp |
|---|
| at 460/480 V at 50 °C rated value | 60 hp |
|---|
| at 575/600 V at 50 °C rated value | 75 hp |
|---|
| contact rating of auxiliary contacts according to UL | R300-B300 |
|---|
| protection class IP on the front according to IEC 60529 | IP00; IP20 with cover |
|---|
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front with cover |
|---|
| IECEx | Yes |
|---|
| 1/L1 | 3/L2 |
|---|
| 5/L3 | A1 |
|---|
| 13 NO | 23 NO |
|---|
| DI 1 | DI 2 |
|---|
| DI 3 | DI 4 |
|---|
| 98 NO | 96 NC |
|---|