Especificaciones técnicas
Protección y seguridad
| Reverse polarity protection | Yes |
|---|---|
| Short-circuit protection | Yes |
| Isolation tested with | 707 V DC (type test) |
Datos eléctricos
| Mains/voltage failure stored energy time | 10 ms |
|---|---|
| Current consumption (rated value) | 350 mA |
| Current consumption, max. | 450 mA |
| Inrush current, max. | 1A |
| Power loss, typ. | 1.8 W |
| Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Entradas/Salidas y comunicación
| PROFINET from GSD version/GSD revision | GSDML V2.45 |
|---|---|
| Number of PROFINET interfaces | 1; 2 ports (switch) |
| RJ 45 (Ethernet) | Yes; with BusAdapter |
| BusAdapter (PROFINET) | Yes; BA 2x RJ45, BA 2x FC, BA 2x M12 |
| PROFINET IO device | Yes |
| Supports protocol for PROFINET IO | Yes |
| PROFIsafe | Yes |
| between PROFINET and all other circuits | Yes; 1500 V AC (type test) |
| PROFINET Security Class | 1 |
Otras características
| Product type designation | IM 155-6 PN ST incl. BA 2x RJ45 and server module |
|---|---|
| Firmware version | V6.4.0 |
| FW update possible | Yes |
| Vendor identification (VendorID) | 002AH |
| Device identifier (DeviceID) | 0313H |
| Device ID according to ODVA (Product code) | 0FA2H |
| I&M data | Yes; I&M0 to I&M4 |
| Module swapping during operation (hot swapping) | Yes; Multi-hot swapping |
| IRT | Yes |
| Local coupling, IO data | Yes |
| Number of coupling modules | 6; 1x output + max. 5x input |
| STEP 7 TIA Portal configurable/integrated from version | V20 |
| STEP 7 configurable/integrated from version | V5.7 SP3 |
| via dataset | Yes |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| I²t | 0.05 A²·s |
| Address space per module, max. | 288 byte; For input and output data respectively |
| Address space per station, max. | 1 440 byte |
| Quantity of operable ET 200SP modules, max. | 32 |
| Quantity of operable ET 200AL modules, max. | 16 |
| Number of submodules per station, max. | 256 |
| Transmission procedure | 100BASE-TX |
| Number of ports | 2; with BusAdapter |
| integrated switch | Yes |
| Open IE communication | Yes |
| Media redundancy | Yes; PROFINET MRP client |
| Dynamic Frame Packing (DFP) | Yes |
| Fast Forwarding | Yes |
| Fragmentation | Yes |
| PROFIenergy | Yes |
| Prioritized startup | Yes |
| Shared device | Yes |
| Number of IO Controllers with shared device, max. | 4 |
| 100 Mbps | Yes |
| Autonegotiation | Yes |
| Autocrossing | Yes |
| MRP | Yes |
| MRPD | Yes |
| TCP/IP | Yes |
| UDP | Yes |
| SNMP | Yes |
| LLDP | Yes |
| ARP | Yes |
| IGMP | Yes |
| Multicast | Yes |
| Broadcast | Yes |
| IPv4 | Yes |
| Status indicator | Yes |
| Alarms | Yes |
| Diagnostics function | Yes |
| RUN LED | Yes; green LED |
| ERROR LED | Yes; red LED |
| MAINT LED | Yes; Yellow LED |
| Connection display LINK TX/RX | Yes; 2x green link LEDs on BusAdapter |
| between different circuits | Safety extra low voltage SELV |
| Network loading class | 3 |
| signed firmware update | Yes |
| safely removing data | Yes |
| data integrity | Yes |
| horizontal installation, min. | -30 °C; No condensation |
| horizontal installation, max. | 60 °C |
| vertical installation, min. | -30 °C; No condensation |
| vertical installation, max. | 50 °C |
| dew point, min. | -60 °C; suitable for dry room applications |
| via BU/BA Send | Yes; + 16 ET 200AL modules |
| Strain relief | Yes; Optional |
| Width | 50 mm |
| Height | 117 mm |
| Depth | 74 mm |
| Weight, approx. | 120 g; without BusAdapter |
| last modified: | 6/18/2026 |