Especificaciones técnicas
Protección y seguridad
| Reverse polarity protection | Yes |
|---|---|
| Short-circuit protection | Yes; electronic/thermal |
| Short-circuit | Yes |
| Isolation tested with | 707 V DC (type test) |
Datos eléctricos
| Current consumption, max. | 50 mA; without load |
|---|---|
| Power loss, typ. | 1.5 W |
| permissible voltage at input, min. | -30 V; -5 V continuous, -30 V brief reverse polarity protection |
| permissible voltage at input, max. | 30 V |
| Current-sinking | Yes; push-pull outputs for 24 V PTO outputs |
| Current-sourcing | Yes |
| for signal "1" minimum load current | 2 mA |
| for signal "0" residual current, max. | 0.5 mA |
| Current per module, max. | 1.4 A |
| Monitoring the supply voltage | Yes |
| Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Entradas/Salidas y comunicación
| PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
|---|---|
| PROFINET from GSD version/GSD revision | GSDML V2.35 |
| PTO (pulse train output) signal interface | Yes |
| For signal interface 24 V asymmetrical | 200 kHz; For 24 V PTO outputs |
| Number of RS 485 interfaces | 0 |
| to standard PROFIBUS master | Yes; Via control and feedback interface |
| to standard PROFINET controller | Yes; Via control and feedback interface |
Detección y sensórica
| Incremental encoder (A, B phase shift) | Yes |
|---|---|
| Incremental encoder (A, B phase shift, quadruple) | Yes |
Montaje y material
| Color code for module-specific color-coded label | CC00 |
|---|
Condiciones ambientales
| Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
|---|
Certificados y homologaciones
| Type Examination Cer | Miscellaneous |
|---|
Otras características
| Product type designation | TM PTO 2x24V |
|---|---|
| usable BaseUnits | BU type A0 |
| I&M data | Yes; I&M0 to I&M3 |
| Isochronous mode | Yes |
| STEP 7 TIA Portal configurable/integrated from version | STEP 7 V17 with HSP or higher |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Inputs | 32 byte |
| Outputs | 16 byte |
| Automatic encoding | Yes |
| Mechanical coding element | Yes |
| Number of digital inputs | 6; 3 per channel |
| Digital inputs, parameterizable | Yes |
| Synchronization | Yes |
| Probe | Yes |
| Drive ready | Yes |
| for signal "0" | -5 ... +5 V |
| for signal "1" | +11 to +30V |
| for signal "1", typ. | 2.5 mA |
| parameterizable | Yes; none / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms |
| shielded, max. | 1 000 m |
| unshielded, max. | 600 m |
| Number of digital outputs | 6; 3 per channel |
| Digital outputs, parameterizable | Yes |
| Response threshold, typ. | 1A |
| Controlling a digital input | Yes |
| 24 V asymmetrical | Yes |
| Pulse and direction | Yes |
| Count up, count down | Yes |
| lower limit | 240 Ω; 48 ohms for CHn.ED |
| upper limit | 12 kΩ |
| for signal "1", min. | 23.2 V; L+ (-1.3 V), L+ (-0.8 V) for CHn.ED |
| for signal "1" rated value | 0.1 A; 0.5 A for CHn.ED |
| for signal "1" permissible range, max. | 0.12 A; 0.6 A for CHn.ED |
| Diagnostic alarm | Yes |
| Channel status display | Yes; green LED |
| for module diagnostics | Yes; green/red DIAG LED |
| between the channels and backplane bus | Yes |
| horizontal installation, min. | -30 °C |
| horizontal installation, max. | 60 °C; Observe derating |
| vertical installation, min. | -30 °C |
| vertical installation, max. | 50 °C; Observe derating |
| dew point, min. | -60 °C; suitable for dry room applications |
| to SIMATIC S7-300 | Yes; Via control and feedback interface |
| to SIMATIC S7-400 | Yes; Via control and feedback interface |
| to SIMATIC S7-1200 | Yes |
| to SIMATIC S7-1500 | Yes |
| Width | 15 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Weight, approx. | 45 g |
| last modified: | 1/22/2026 |