Especificaciones técnicas
Protección y seguridad
| Short-circuit protection | Yes |
|---|---|
| Reverse polarity protection | Yes; against destruction |
| short-circuit | Yes |
| Isolation tested with | 707 V DC (type test) |
Datos eléctricos
| Current consumption, max. | 70 mA; without load |
|---|---|
| Output current, max. | 300 mA |
| Power loss, typ. | 1.7 W |
| Type of input voltage | DC |
| permissible voltage at input, min. | -30 V; -5 V continuous, -30 V brief reverse polarity protection |
| permissible voltage at input, max. | 30 V |
| Current-sinking | Yes |
| Current-sourcing | Yes |
| Limitation of inductive shutdown voltage to | -0.8 V |
| Current measurement | Yes |
| Current control | Yes |
| Type of output voltage | DC |
| Current per channel, max. | 2A |
| Current per group, max. | 4A |
| Current per module, max. | 4A |
| Monitoring the supply voltage | Yes |
| Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Entradas/Salidas y comunicación
| PROFIBUS from GSD version/GSD revision | GSD Revision 5 |
|---|---|
| PROFINET from GSD version/GSD revision | GSDML V2.31 |
| Number of RS 485 interfaces | 0 |
| to standard PROFIBUS master | Yes |
| to standard PROFINET controller | Yes |
Montaje y material
| Color code for module-specific color-coded label | CC40 |
|---|
Otras características
| Product type designation | TM Pulse 2x24 V |
|---|---|
| HW functional status | From FS03 |
| Firmware version | V1.0 |
| FW update possible | Yes |
| usable BaseUnits | BU type B1 |
| I&M data | Yes; I&M 0 |
| Isochronous mode | Yes |
| STEP 7 TIA Portal configurable/integrated from version | V13 SP1 + HSP |
| STEP 7 configurable/integrated from version | V5.5 SP4 and higher |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Number of outputs | 2; A common 24V encoder supply for both channels |
| 24 V | Yes; L+ (-0.8 V) |
| Inputs | 16 byte; 8 per channel |
| Outputs | 24 byte; 12 per channel |
| Automatic encoding | Yes |
| Mechanical coding element | Yes |
| Type of mechanical coding element | type C |
| Number of digital inputs | 2; 1 per channel |
| Digital inputs, parameterizable | Yes |
| Freely usable digital input | Yes |
| HW enable for digital output | Yes |
| for signal "0" | -5 ... +5 V |
| for signal "1" | +11 to +30V |
| for signal "1", typ. | 2.5 mA |
| parameterizable | Yes; none / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms |
| Type of digital output | P- and M-switching |
| Number of digital outputs | 2; 1 per channel |
| Digital outputs, parameterizable | Yes |
| Response threshold, typ. | 6.8 A with Standard output, 2 A with High Speed output |
| Controlling a digital input | Yes |
| Accuracy of pulse duration | ±100 ppm ±0.5 µs with High Speed output, ±100 ppm ±9 µs with Standard |
| minimum pulse duration | 1.5 µs; With High Speed output, 10 µs with Standard output |
| Freely usable digital output | Yes |
| PWM output | Yes |
| Number, max. | 2; 1 per channel |
| Cycle duration, parameterizable | Yes; Max. 85 s |
| Resolution of the duty cycle | 0.0036 %; For S7 analog format, min. 20 ns |
| Connection of a proportional valve | Yes |
| Dithering | Yes |
| Frequency adjustable | Yes |
| Amplitude adjustable | Yes |
| Connection of a DC motor | Yes |
| ON-delay | Yes |
| OFF-delay | Yes |
| Frequency output | Yes |
| Pulse train | Yes |
| Pulse output | Yes |
| lower limit | 12 Ω; 240 ohm with High Speed output |
| upper limit | 12 kΩ |
| for signal "0", max. | 1V |
| for signal "1", min. | 23.2 V; L+ (-0.8 V) |
| for signal "1" rated value | 2 A; 0.1 A with High Speed output, observe derating |
| "0" to "1", typ. | 0 µs; With High Speed output, 4.5 µs with Standard output |
| "0" to "1", max. | 0.8 µs; With High Speed output, 9 µs with Standard output |
| "1" to "0", typ. | 0 µs; With High Speed output, 4.5 µs with Standard output |
| "1" to "0", max. | 0.8 µs; With High Speed output, 9 µs with Standard output |
| for uprating | Yes |
| Jitter, max. | 1 µs; typically ± |
| Diagnostics function | Yes |
| Substitute values connectable | Yes; Parameterizable |
| Diagnostic alarm | Yes |
| Channel status display | Yes |
| for module diagnostics | Yes; green/red DIAG LED |
| between the channels and backplane bus | Yes |
| horizontal installation, min. | -30 °C |
| horizontal installation, max. | 60 °C; Observe derating |
| vertical installation, min. | -30 °C |
| vertical installation, max. | 50 °C; Observe derating |
| dew point, min. | -60 °C; suitable for dry room applications |
| to SIMATIC S7-300 | Yes |
| to SIMATIC S7-400 | Yes |
| to SIMATIC S7-1200 | Yes |
| to SIMATIC S7-1500 | Yes |
| Width | 20 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Weight, approx. | 50 g |
| tificate | ate |
| other | Environment |
| last modified: | 4/23/2026 |