€227,56 EUR
+ VAT
Especificaciones técnicas
Protección y seguridad
| Reverse polarity protection | Yes |
|---|---|
| Short-circuit protection | Yes |
| Short-circuit | Yes; module-wise |
| Isolation tested with | 707 V DC (type test) |
Datos eléctricos
| Current consumption, max. | 50 mA; without load |
|---|---|
| Power loss, typ. | 2.5 W; at 24 V, 25 °C, DQ mode, 2 A per channel |
| Current-sourcing | Yes; Push-pull output |
| Limitation of inductive shutdown voltage to | M (-1 V) |
| for signal "0" residual current, max. | 0.1 mA |
| Current per channel, max. | 2A |
| Current per module, max. | 8A |
| Monitoring the supply voltage | Yes |
| Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Entradas/Salidas y comunicación
| PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
|---|---|
| PROFINET from GSD version/GSD revision | GSDML V2.33 |
Montaje y material
| Color code for module-specific color-coded label | CC00 |
|---|
Condiciones ambientales
| Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
|---|
Otras características
| Product type designation | DQ 4x24 V DC/2 A HS |
|---|---|
| HW functional status | From FS05 |
| FW update possible | Yes |
| usable BaseUnits | BU type A0 |
| I&M data | Yes; I&M0 to I&M3 |
| Isochronous mode | Yes; Operating modes DQ and OVS only |
| STEP 7 TIA Portal configurable/integrated from version | STEP 7 V15.1 or higher |
| STEP 7 configurable/integrated from version | via GSD as of V5.6 HF4 |
| DQ with energy-saving function | Yes; Valve control |
| PWM | Yes |
| Cam control (switching at comparison values) | Yes; Via MtM (module-to-module communication) |
| Oversampling | Yes |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Inputs | 1 byte; Max. 14 bytes in the cam control operating mode |
| Outputs | 1 byte; Max. 16 bytes in the oversampling operating mode |
| Automatic encoding | Yes |
| Mechanical coding element | Yes |
| Type of mechanical coding element | Type A |
| 2-wire connection | BU type A0 |
| 3-wire connection | BU type A0 with AUX terminals or potential distributor module |
| 4-wire connection | BU type A0 + Potential distributor module |
| Type of digital output | Source output (PNP, current-sourcing) |
| Number of digital outputs | 4 |
| Digital outputs, parameterizable | Yes |
| Response threshold, typ. | 6A |
| Switching tripped by comparison values | Yes |
| Number of cam tracks, max. | 4 |
| Number of cams per module, max. | 16 |
| Number of cams per track, max. | 16 |
| Supported axis types | Linear axes and rotary axes with modulo function |
| Hysteresis | Yes |
| Pulsed cam output | Yes |
| Range of values for comparison values, max. | -2,147,483,648 to 2,147,483,647 (user-specific within this range) |
| Freely usable digital output | Yes |
| PWM output | Yes |
| Number, max. | 4 |
| Resolution of the duty cycle | 0.1 % |
| Digital output with oversampling | Yes |
| Values per cycle, max. | 32 |
| Resolution, min. | 100 µs |
| lower limit | 12 Ω |
| upper limit | 3 400 Ω |
| for signal "1" rated value | 2A |
| "0" to "1", max. | 1 µs |
| "1" to "0", max. | 1 µs |
| up to 30 °C, max. | 8 A; DQ mode |
| up to 40 °C, max. | 6.9 A; DQ mode |
| up to 50 °C, max. | 4.7 A; DQ mode |
| up to 60 °C, max. | 2.5 A; DQ mode |
| shielded, max. | 50 m |
| unshielded, max. | 50 m |
| Execution and activation time (TCO), min. | 40 µs |
| Bus cycle time (TDP), min. | 125 µs |
| Jitter, max. | 1 µs |
| Diagnostics function | Yes |
| Substitute values connectable | Yes |
| Diagnostic alarm | Yes |
| Diagnostic information readable | Yes |
| Group error | Yes |
| Channel status display | Yes; green LED |
| for module diagnostics | Yes; green/red DIAG LED |
| between the channels and backplane bus | Yes |
| horizontal installation, min. | -30 °C |
| horizontal installation, max. | 60 °C |
| vertical installation, min. | -30 °C |
| vertical installation, max. | 50 °C |
| dew point, min. | -60 °C; suitable for dry room applications |
| Width | 15 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Weight, approx. | 31 g |
| last modified: | 3/10/2026 |