Especificaciones técnicas
Protección y seguridad
| Short-circuit protection | Yes |
|---|
Datos eléctricos
| Type of supply voltage | DC |
|---|---|
| Current consumption (rated value) | 0.3 A |
| Current per channel, max. | 100 mA |
| Current per group, max. | 800 mA |
Entradas/Salidas y comunicación
| Number of industrial Ethernet interfaces | 2; For the construction of lines and rings without external switch |
|---|---|
| Number of PROFINET interfaces | 2; Incl. switch |
| Industrial Ethernet status LED | 2; Per port |
| PROFINET | Yes; also 3rd party PLC |
| Supports protocol for PROFINET IO | Yes |
Montaje y material
| Number of color modes for LED | 5; red, green, blue, yellow, white |
|---|
Certificados y homologaciones
| CE mark | Yes |
|---|---|
| cULus | Yes |
| RCM (formerly C-TICK) | Yes |
| KC approval | Yes |
| ATEX Zone 2 | Yes |
| ATEX Zone 22 | Yes |
| cULus Class I Zone 2, Division 2 | Yes |
| FM Class I Division 2 | Yes |
| China RoHS | FM |
Otras características
| Product type designation | KP8 PN |
|---|---|
| user-definable label membrane keys | Yes |
| Number of function keys | 8 |
| Number of short-stroke keys | 8 |
| DP direct LEDs (LEDs as S7 output I/O) | 8; Adjustable brightness |
| Direct keys (keys as S7 input I/O) | 8 |
| Mounting type | Clamp terminals |
| Mounting position | vertical |
| Front mounting | Yes; Compatible with Extension Units dimensions |
| Mounting in portrait format possible | Yes |
| Mounting in landscape format possible | Yes |
| Number of slots for command devices and signaling units | 0 |
| Rated value (DC) | 24 V; 24 V looped through at connector, no interruption on pulling |
| permissible range, lower limit (DC) | 20.4 V |
| permissible range, upper limit (DC) | 28.8 V |
| Number of digital inputs | 8; Max. 8 inputs and outputs (total) |
| Number of digital outputs | 8; Max. 8 inputs and outputs (total) |
| Number of ports of the integrated switch | 2; Per port |
| IRT | Yes |
| MRP | Yes |
| Illuminant test | Yes; During switch on |
| Key and signal lamp test | Yes; automatically when switching on |
| Limit class A, for use in industrial areas | Yes; Group 1, measured at a distance of 10 m |
| IP (at the front) | IP65 |
| IP (rear) | IP20 |
| Enclosure Type 4x at the front | Yes; Incl. NEMA12 |
| min. | 0 °C |
| max. | 55 °C |
| For vertical installation, min. | 0 °C |
| For vertical installation, max. | 55 °C |
| Operation, max. | 95 %; no condensation |
| STEP 7 Basic (TIA Portal) | Yes |
| STEP 7 Professional (TIA Portal) | Yes |
| S7-1200 | Yes; with ET 200pro CPU and ET 200S CPU |
| S7-1500 | Yes |
| S7-300/400 | Yes; STEP 7 or SIMATIC STEP 7 Basic V11 or higher |
| WinAC | Yes |
| Plastic | Yes |
| Short-stroke keys (in switching cycles) | 1 500 000 |
| LEDs (ON period) | 100 % |
| Width of the housing front | 98 mm |
| Height of housing front | 155 mm |
| Mounting cutout, width | 67.7 mm; Max. thickness of mounting plate 2 - 6 mm |
| Mounting cutout, height | 129.7 mm |
| mounting depth | 49 mm; Incl. angled SIMATIC Ethernet connector |
| EMV | For use in hazardous locations |
| For use in hazardous locations | Maritime application |
| okai | tion Society) |
| KR (Korean Register | PROFINET |
| last modified: | 4/14/2025 |