Especificaciones técnicas
Protección y seguridad
| Reverse polarity protection | Yes |
|---|---|
| Short-circuit protection | Yes |
| Short-circuit | Yes |
| Isolation tested with | 707 V DC (type test) |
| Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
Datos eléctricos
| Current consumption (rated value) | 70 mA |
|---|---|
| Output voltage (DC) | 4.85 V |
| Power consumption from the backplane bus | 65 mW |
| Power loss, typ. | 1.5 W |
| Interference voltage suppression for interference | 60 / 50 Hz / no |
| Voltage, relative to input range, (+/-) | 0.05 %; See manual for details |
| Monitoring the supply voltage | Yes |
| Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| between the channels and the power supply of the | Yes |
Montaje y material
| Color code for module-specific color-coded label | CC00 |
|---|
Condiciones ambientales
| Installation altitude above sea level, max. | 5 000 m |
|---|
Otras características
| Product type designation | AI 2xSG 4-/6-wire HS |
|---|---|
| FW update possible | Yes |
| based on | 7MH4134-6LB00-0DA0 |
| usable BaseUnits | BU type A0 |
| I&M data | Yes; I&M0 to I&M3 |
| Isochronous mode | Yes |
| Measuring range scalable | Yes |
| Adjustment of measuring range | Yes; ±0.5 ... 320 mV/V |
| STEP 7 TIA Portal configurable/integrated from version | see entry ID: 109746275 |
| Oversampling | Yes; 2 channels per module |
| Reparameterization possible in RUN | Yes |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Address space per module, max. | 32 byte |
| Inputs | 32 byte |
| Outputs | 8 byte |
| Automatic encoding | Yes |
| Mechanical coding element | Yes |
| Type of mechanical coding element | Type A |
| Number of analog inputs | 2; Differential inputs |
| Cycle time (all channels), min. | 100 µs |
| Analog input with oversampling | Yes |
| Values per cycle, max. | 14 |
| Resolution, min. | 100 µs |
| Strain gauges (full bridges) | Yes |
| shielded, max. | 500 m |
| Measurement principle | Sigma Delta |
| Resolution with overrange (bit including sign), max. | 28 bit; 16 bits with oversampling |
| Integration time, parameterizable | Yes |
| Conversion time (per channel) | 100 µs |
| IIR low-pass filter frequency | 0.01 ... 600 Hz |
| IIR low-pass filter ordinal number | 1 ... 4 |
| Notch filter frequency | 0.1 ... 1 000 Hz |
| Notch filter quality | 5.00 ... 250.00 |
| Average value filter | 0.1 ... 655.3 ms |
| For strain gauges (full bridges) with 4-conductor | Yes |
| For strain gauges (full bridges) with 6-conductor | Yes |
| Resistance of full bridge, min. | 80 Ω |
| Resistance of full bridge, max. | 5 000 Ω |
| Linearity error (relative to input range), (+/-) | 0.025 % |
| Temperature error (relative to input range), (+/-) | 0.0005 %/°C; Strain gauge full bridge, 6-conductor connection |
| Temperature coefficient, zero point | ≤ ±0.25 μV/K |
| Filtering and processing time (TCI), min. | 87 µs |
| Bus cycle time (TDP), min. | 125 µs |
| Diagnostics function | Yes; Diagnostic alarm |
| Diagnostic alarm | Yes; Parameterizable |
| Limit value alarm | Yes; two upper and two lower limit values in each case |
| Wire break | Yes |
| Group error | Yes |
| Overflow/Underflow | Yes |
| Channel status display | Yes; green LED |
| for channel diagnostics | Yes; red LED |
| for module diagnostics | Yes; green/red DIAG LED |
| between the channels and backplane bus | Yes |
| horizontal installation, min. | -40 °C; = Tmin (incl. condensation/frost) |
| horizontal installation, max. | 60 °C; = Tmax; +70 °C with spacing modules (6AG1193-6BN00-7BA0) or |
| vertical installation, min. | -40 °C; = Tmin |
| vertical installation, max. | 50 °C; = Tmax |
| 2-38, max. | horizontal installation |
| Resistant to commercially available coolants and | Yes; Incl. diesel and oil droplets in the air |
| 60721-3-3 | Class 3B3 on request |
| to EN 60721-3-3 | 0AA0//6AG1193-6AB00-0AA0) |
| 60721-3-6 | degree 3). |
| to EN 60721-3-6 | 0AA0/6AG1193-6AB00-0AA0) |
| Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
| Qualification and Performance of Electrical Insulating | Yes; Conformal coating, Class A |
| Width | 15 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Weight, approx. | 30 g |
| last modified: | 10/23/2025 |