Especificaciones técnicas
Generalidades
| Series mode interference (peak value of interference < | 70 dB |
|---|
Protección y seguridad
| Reverse polarity protection | Yes |
|---|---|
| Isolation tested with | 707 V DC (type test) |
| Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
Datos eléctricos
| Current consumption (rated value) | 37 mA |
|---|---|
| Current consumption, max. | 50 mA |
| Power loss, typ. | 0.9 W |
| permissible input voltage for voltage input (destruction limit), | 30 V |
| Interference voltage suppression for interference | 16.6 / 50 / 60 Hz / off |
| for voltage measurement | Yes |
| Voltage, relative to input range, (+/-) | 0.2 %; 0.5 % when voltage frequency converter OFF |
| Common mode voltage, max. | 60 V; DC |
| Monitoring the supply voltage | Yes |
| Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| between the channels and the power supply of the | Yes |
Montaje y material
| Color code for module-specific color-coded label | CC00 |
|---|
Condiciones ambientales
| Installation altitude above sea level, max. | 5 000 m |
|---|
Certificados y homologaciones
| China RoHS | CCC-Ex |
|---|
Otras características
| Product type designation | AI 4xTC HS |
|---|---|
| FW update possible | Yes |
| based on | 6ES7134-6JD00-0DA1 |
| usable BaseUnits | BU type A0, A1 |
| I&M data | Yes; I&M0 to I&M3 |
| Measuring range scalable | Yes |
| STEP 7 TIA Portal configurable/integrated from version | see entry ID: 109746275 |
| MSI | Yes |
| Reparameterization possible in RUN | Yes |
| Calibration possible in RUN | Yes |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Address space per module, max. | 16 byte; + 1 byte for QI information |
| Automatic encoding | Yes |
| Mechanical coding element | Yes |
| Type of mechanical coding element | Type A |
| 2-wire connection | BU type A0, A1 |
| Number of analog inputs | 4 |
| Technical unit for temperature measurement adjustable | Yes; °C/°F/K |
| 1 V to +1 V | Yes; 16 bit incl. sign |
| Input resistance (-1 V to +1 V) | 1 MΩ |
| 250 mV to +250 mV | Yes; 16 bit incl. sign |
| Input resistance (-250 mV to +250 mV) | 1 MΩ |
| 50 mV to +50 mV | Yes; 16 bit incl. sign |
| Input resistance (-50 mV to +50 mV) | 1 MΩ |
| 80 mV to +80 mV | Yes; 16 bit incl. sign |
| Input resistance (-80 mV to +80 mV) | 1 MΩ |
| type B | Yes; 16 bit incl. sign |
| Input resistance (Type B) | 1 MΩ |
| type C | Yes; 16 bit incl. sign |
| Input resistance (Type C) | 1 MΩ |
| Type E | Yes; 16 bit incl. sign |
| Input resistance (Type E) | 1 MΩ |
| Type J | Yes; 16 bit incl. sign |
| Input resistance (type J) | 1 MΩ |
| Type K | Yes; 16 bit incl. sign |
| Input resistance (Type K) | 1 MΩ |
| Type L | Yes; 16 bit incl. sign |
| Input resistance (Type L) | 1 MΩ |
| Type N | Yes; 16 bit incl. sign |
| Input resistance (Type N) | 1 MΩ |
| Type R | Yes; 16 bit incl. sign |
| Input resistance (Type R) | 1 MΩ |
| Type S | Yes; 16 bit incl. sign |
| Input resistance (Type S) | 1 MΩ |
| Type T | Yes; 16 bit incl. sign |
| Input resistance (Type T) | 1 MΩ |
| Type U | Yes; 16 bit incl. sign |
| Input resistance (Type U) | 1 MΩ |
| Type TXK/TXK(L) to GOST | Yes; 16 bit incl. sign |
| Input resistance (Type TXK/TXK(L) to GOST) | 1 MΩ |
| Parameterizable | Yes |
| internal comparison point | Yes; with BaseUnit type A1 |
| Reference channel of the group | Yes |
| Number of reference channel groups | 4; Group 0 to 3 |
| fixed reference temperature | Yes |
| shielded, max. | 200 m; 100 m for thermocouples |
| Measurement principle | integrating (Sigma-Delta) |
| Resolution with overrange (bit including sign), max. | 16 bit |
| Integration time, parameterizable | Yes |
| additional processing time for wire-break check | 1 ms |
| Conversion time (per channel) | 180/60/50/1.25 ms |
| Number of smoothing levels | 4; None; 4/8/16 times |
| Step: None | Yes |
| Step: low | Yes |
| Step: Medium | Yes |
| Step: High | Yes |
| Linearity error (relative to input range), (+/-) | 0.01 % |
| Temperature error (relative to input range), (+/-) | 0.005 %/K |
| Crosstalk between the inputs, min. | -70 dB |
| Common mode interference, min. | 90 dB |
| Diagnostics function | Yes |
| Diagnostic alarm | Yes |
| Limit value alarm | Yes; two upper and two lower limit values in each case |
| Wire break | Yes; channel by channel |
| Group error | Yes |
| Overflow/Underflow | Yes; channel by channel |
| Channel status display | Yes; green LED |
| for channel diagnostics | Yes; red LED |
| for module diagnostics | Yes; green/red LED |
| between the channels and backplane bus | Yes |
| between the inputs (UCM) | 60 V DC |
| Suitable for applications according to AMS 2750 | Yes; Declaration of Conformity, see online support entry 109757262 |
| Suitable for applications according to CQI-9 | Yes; Based on AMS 2750 E |
| horizontal installation, min. | -40 °C; = Tmin (incl. condensation/frost) |
| vertical installation, min. | -40 °C; = Tmin (incl. condensation/frost) |
| vertical installation, max. | 50 °C; = Tmax |
| 2-38, max. | conditions) |
| Resistant to commercially available coolants and | Yes; Incl. diesel and oil droplets in the air |
| 60721-3-3 | Class 3B3 on request |
| to EN 60721-3-3 | 0AA0) |
| 60721-3-6 | request |
| to EN 60721-3-6 | 0AA0) |
| conditions acc. to EN 60721, EN 60654-4 and | during operation! |
| Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
| Qualification and Performance of Electrical Insulating | Yes; Conformal coating, Class A |
| Width | 15 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Weight, approx. | 33 g |
| EMV | For use in hazardous locations |
| last modified: | 10/23/2025 |