Especificaciones técnicas
Protección y seguridad
| opto-electronic protection device monitoring | Yes |
|---|---|
| performance level (PL) according to EN ISO 13849-1 | e |
| category according to EN ISO 13849-1 | 4 |
| according to ISO 13849-1 | PL e |
| device type according to ISO 13849-1 | 1 |
| according to IEC 61508 | 3 |
| PFHD with high demand rate according to IEC 61508 | 1.2E-8 1/h |
| PFDavg with low demand rate according to IEC 61508 | 1.8E-5 |
| touch protection against electrical shock | finger-safe |
Datos eléctricos
| insulation voltage rated value | 50 V |
|---|---|
| surge voltage resistance rated value | 800 V |
| input voltage at digital input at DC rated value | 24 V |
| switching capacity current of semiconductor outputs at DC-13 at | 4A |
| total current maximum | 7A |
| voltage drop maximum | 0.5 V |
| type of voltage | DC |
| control supply voltage rated value | 24 V |
| operating power rated value | 4.5 W |
Entradas/Salidas y comunicación
| PROFIBUS DP protocol | Yes; when using the DP interface module; 64 bit cyclical data |
|---|---|
| PROFINET IO protocol | Yes; when using the PN interface module; 64-bit cyclic data |
Detección y sensórica
| monitoring of floating sensors | Yes |
|---|---|
| monitoring of non-floating sensors | Yes |
| muting, 2 sensor-parallel | Yes |
| muting, 4 sensor-parallel | Yes |
| muting, 4 sensor-sequential | Yes |
| for testing contact-based sensors | 4 |
Conexión y cableado
| product function removable terminal | Yes |
|---|---|
| for AWG cables solid | 1x (20 ... 16), 2x (20 ... 16) |
| for AWG cables stranded | 1x (20 ... 16), 2x (20 ... 16) |
Condiciones ambientales
| vibration resistance according to IEC 60068-2-6 | 5 ... 500 Hz: 0.75 mm |
|---|---|
| installation altitude at height above sea level maximum | 4 000 m |
Otras características
| product brand name | SIRIUS |
|---|---|
| product category | Safety relay |
| design of the product | 20 F-DI, 4 F-DQ, 2 DQ |
| suitability for use for monitoring of optoelectronic | Yes |
| position switch monitoring | Yes |
| EMERGENCY-OFF circuit monitoring | Yes |
| valve monitoring | Yes |
| magnetically operated switch monitoring | Yes |
| proximity switch monitoring | Yes |
| safety-related circuits | Yes |
| EMERGENCY STOP function | Yes |
| protective door monitoring | Yes |
| protective door monitoring with tumbler | Yes |
| monitoring parameterizable | Yes |
| evaluation: electro-sensitive protective equipment | Yes |
| evaluation: selector switch | Yes |
| pressure-sensitive mat monitoring | Yes |
| evaluation: two-hand operator panel | Yes |
| evaluation: enabling switch | Yes |
| monitored start-up | Yes |
| two-hand control according to EN 574 | Yes |
| configuration software required | Yes; Safety ES V1.0 and higher |
| number of function blocks typical | 50 |
| degree of pollution | 3 |
| shock resistance | 15 g / 11 ms |
| operating frequency maximum | 2 000 1/h |
| Net Weight | 0.358 kg |
| relative humidity during operation | 10 ... 95 % |
| air pressure according to SN 31205 | 90 ... 106 kPa |
| EMC emitted interference according to IEC 60947-1 | class A |
| due to burst according to IEC 61000-4-4 | 2 kV (power ports) / 1 kV (signal ports) |
| field-based interference according to IEC 61000-4-3 | 10 V/m |
| electrostatic discharge according to IEC 61000-4-2 | 4 kV contact discharge / 8 kV air discharge |
| stop category according to IEC 60204-1 | 0/1 |
| SIL Claim Limit (subsystem) according to EN 62061 | 3 |
| according to IEC 62061 | SIL 3 |
| Safe failure fraction (SFF) | 99 % |
| parameterizable inputs | Yes |
| parameterizable outputs | Yes |
| safety-related | 20 |
| non-safety-related | 0 |
| input delay time | 0 ... 150 ms |
| type of digital inputs according to IEC 60947-1 | Type 1 |
| ingress aquisition time at digital input maximum | 60 ms |
| input delay time at digital input maximum | 150 ms |
| for signal <1> typical | 2.6 mA |
| safety-related 2-channel | 4 |
| 1-channel | 0 |
| 2-channel | 0 |
| recovery time of the safe outputs | 0 ms |
| readback time maximum | 400 ms |
| light test period | 3 ms |
| dark period of the common drivers | 3 ms |
| shielded maximum | 1 000 m |
| unshielded maximum | 600 m |
| initial value | 0.85 |
| full-scale value | 1.2 |
| mounting position | any |
| fastening method | Snap-mounted to DIN rail or screw-mounted with additional push-in lug |
| height | 100 mm |
| width | 45 mm |
| depth | 124.5 mm |
| type of electrical connection | spring-loaded terminal (push-in) |
| solid | 1x (0.5 ... 1.5 mm²), 2x (0.5 ... 1.5 mm²) |
| finely stranded with core end processing | 1x (0.5 ... 1.0 mm²), 2x (0.5 ... 1.0 mm²) |
| stranded | 20 ... 16 |
| tificate | ates/Test Report |
| last modified: | X1 |
| Page 5/6 | FE |
| F-Q1 | T1_2 |
| F-Q2 | F-IN7 |
| F-Q3 | F-IN15 |