SIRIUS Relé de seguridad; Módulo de ampliación de entrada para sensores; 24 V DC; conexión Push-In

🔌 ComunicaciónYes; when using the PN interface module; 64-bit cyclic data
Protección y seguridad
performance level (PL) according to EN ISO 13849-1e
category according to EN ISO 13849-14
according to ISO 13849-1PL e
at single-channel evaluation according to ISO 13849-1c
at 2-channel evaluation according to ISO 13849-1e
device type according to ISO 13849-11
according to IEC 615083
at single-channel evaluation according to IEC 615081
at 2-channel evaluation according to IEC 615083
PFHD with high demand rate according to IEC 615081E-8 1/h
PFDavg with low demand rate according to IEC 615081.5E-5
of service life according to IEC 6150820 a
Entradas/Salidas y comunicación
PROFIBUS DP protocolYes; when using the DP interface module; 64 bit cyclical data
PROFINET IO protocolYes; when using the PN interface module; 64-bit cyclic data
Conexión y cableado
of the terminalIP20
product function removable terminalYes
for AWG cables solid1x (20 ... 14), 2x (18 ... 16)
for AWG cables stranded1x (20 ... 14), 2x (18 ... 16)
Condiciones ambientales
installation altitude at height above sea level maximum4 000 m
Otras características
product brand nameSIRIUS
product categorySafety relay
design of the product10 F-DI, 2 F-DQ, 1 DQ
suitability for use for monitoring of optoelectronicYes
monitoring of floating sensorsYes
monitoring of non-floating sensorsYes
position switch monitoringYes
EMERGENCY-OFF circuit monitoringYes
valve monitoringYes
opto-electronic protection device monitoringYes
magnetically operated switch monitoringYes
proximity switch monitoringYes
safety-related circuitsYes
EMERGENCY STOP functionYes
protective door monitoringYes
protective door monitoring with tumblerYes
muting, 2 sensor-parallelYes
muting, 4 sensor-parallelYes
muting, 4 sensor-sequentialYes
monitoring parameterizableYes
evaluation: electro-sensitive protective equipmentYes
evaluation: selector switchYes
pressure-sensitive mat monitoringYes
evaluation: two-hand operator panelYes
evaluation: enabling switchYes
monitored start-upYes
two-hand control according to EN 574Yes
configuration software requiredYes; Safety ES V1.0 and higher
number of function blocks typical50
insulation voltage rated value50 V
degree of pollution3
surge voltage resistance rated value800 V
of the enclosureIP20
shock resistance15 g / 11 ms
vibration resistance according to IEC 60068-2-65 ... 500 Hz: 0.75 mm
operating frequency maximum2 000 1/h
Net Weight0.218 kg
during operation-25 ... +60 °C
during storage-40 ... +80 °C
during transport-40 ... +80 °C
relative humidity during operation10 ... 95 %
air pressure according to SN 3120590 ... 106 kPa
EMC emitted interference according to IEC 60947-1class A
due to burst according to IEC 61000-4-42 kV (power ports) / 1 kV (signal ports)
field-based interference according to IEC 61000-4-310 V/m
electrostatic discharge according to IEC 61000-4-24 kV contact discharge / 8 kV air discharge
stop category according to IEC 60204-10/1
SIL Claim Limit (subsystem) according to EN 620613
according to IEC 62061SIL 3
at single-channel evaluation according to IEC 620611
at 2-channel evaluation according to IEC 620613
Safe failure fraction (SFF)99 %
touch protection against electrical shockfinger-safe
parameterizable inputsYes
parameterizable outputsYes
at the digital outputs short-circuit protectionYes
safety-related10
non-safety-related0
input delay time0 ... 150 ms
type of digital inputs according to IEC 60947-1Type 1
ingress aquisition time at digital input maximum60 ms
input delay time at digital input maximum150 ms
input voltage at digital input at DC rated value24 V
for signal <1> typical2.6 mA
safety-related 2-channel2
for testing contact-based sensors2
1-channel0
2-channel0
recovery time of the safe outputs0 ms
readback time maximum400 ms
light test period3 ms
dark period of the common drivers3 ms
maximum0.1 mA
at digital output with signal <0> maximum0.1 mA
total current maximum6.5 A
voltage drop maximum0.5 V
shielded maximum1 000 m
unshielded maximum600 m
type of voltageDC
control supply voltage rated value24 V
initial value0.85
full-scale value1.2
at 24 V10 A
operating power rated value2.5 W
mounting positionany
fastening methodSnap-mounted to DIN rail or screw-mounted with additional push-in lug
height100 mm
width22.5 mm
depth124.5 mm
type of electrical connectionscrew terminal
solid1x (0.5 ... 2.5 mm²), 2x (1.0 ... 1.5 mm²)
finely stranded with core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.0 mm²)
stranded20 ... 14
tificateates/Test Report
A1+T1
F-IN1F-IN3
F-IN5F-IN7
F-IN9T2
F-IN2F-IN4
F-IN6F-IN8