Especificaciones técnicas
Protección y seguridad
| for short-circuit protection of the NO contacts of the relay | gL/gG: 6 A or MCB type C: 1 A |
|---|---|
| for short circuit protection of the NC contacts of the relay | gL/gG: 6 A or MCB type C: 1 A |
| design of the electrical isolation | galvanic isolation |
| protection class IP on the front according to IEC 60529 | IP20 |
Datos eléctricos
| power loss [W] maximum | 2W |
|---|---|
| power loss [V·A] maximum | 5.1 VA |
| surge voltage resistance rated value | 6 kV |
| thermal current of the switching element with contacts | 5A |
| undervoltage detection | Yes |
| overvoltage detection | Yes |
| overvoltage detection 3 phase | Yes |
| undervoltage detection 3 phases | Yes |
| voltage window recognition 3 phase | Yes |
| adjustable open/closed-circuit current principle | Yes |
| type of voltage of the control supply voltage | AC |
| supply voltage frequency rated value | 70 ... 15 Hz |
| measurable voltage 1 at AC | 160 ... 760 V |
| measurable voltage 2 at AC | 90 ... 440 V |
| buffering time in the event of power failure minimum | 20 ms |
| number of poles for main current circuit | 4 |
| operational current at 17 V minimum | 5 mA |
| continuous current of the DIAZED fuse link of the output | 6A |
| between the voltage supply and other circuits | Yes |
Medición y rango
| relative metering precision | 3% |
|---|
Conexión y cableado
| operating frequency with 3RT2 contactor maximum | 5 000 1/h |
|---|---|
| product component removable terminal for main circuit | Yes |
| product component removable terminal for auxiliary and | Yes |
| for AWG cables solid | 1x (20 ... 12) |
| for AWG cables stranded | 20 ... 12 |
Montaje y material
| material of switching contacts | AgSnO2 |
|---|
Condiciones ambientales
| vibration resistance according to IEC 60068-2-6 | 10 ... 55 Hz: 0.35 mm |
|---|---|
| installation altitude at height above sea level maximum | 2 000 m |
Otras características
| product brand name | SIRIUS |
|---|---|
| product type designation | 3UG5 |
| product function | line monitoring |
| design of the display | LCD |
| degree of pollution | 3 |
| for monitoring | AC |
| shock resistance according to IEC 60068-2-27 | sinusoidal half-wave 15 g / 11 ms |
| switching behavior | monostable |
| mechanical service life (operating cycles) typical | 10 000 000 |
| adjustable OFF-delay time | 0.1 ... 30 s |
| relative repeat accuracy | 0% |
| Net Weight | 0.164 kg |
| phase sequence recognition | Yes |
| phase failure detection | Yes |
| asymmetry detection | Yes |
| auto-RESET | Yes |
| neutral conductor monitoring adjustable | Yes |
| initial value | 0.85 |
| full-scale value | 1.1 |
| adjustable operating delay time initial value | 0s |
| when starting | 0.1 ... 999.8 s |
| response time maximum | 500 ms |
| accuracy of digital display | +/-1 digit |
| relative temperature-related measurement deviation | 1% |
| temperature drift per °C | 0 %/°C |
| number of NC contacts delayed switching | 0 |
| number of NO contacts delayed switching | 0 |
| for auxiliary contacts | 2 |
| delayed switching | 2 |
| contact rating of auxiliary contacts according to UL | R300 / B300 |
| EMC emitted interference according to IEC 60947-1 | class A |
| due to burst according to IEC 61000-4-4 | 2 kV (power ports), 2 kV (signal ports) |
| due to conductor-earth surge according to IEC 61000-4-5 | 2 kV |
| due to conductor-conductor surge according to IEC | 1 kV |
| field-based interference according to IEC 61000-4-3 | 10 V/m |
| electrostatic discharge according to IEC 61000-4-2 | 6 kV contact discharge / 8 kV air discharge |
| between input and output | Yes |
| between the outputs | Yes |
| type of electrical connection | spring-loaded terminal (push-in) |
| solid | 1x (0.5 ... 4 mm²) |
| finely stranded with core end processing | 1x (0.5 ... 2.5 mm²) |
| finely stranded without core end processing | 0.5 ... 4 mm² |
| stranded | 20 ... 12 |
| stripped length | 10 mm |
| mounting position | any |
| fastening method | screw and snap-on mounting onto 35 mm DIN rail |
| height | 100 mm |
| width | 22.5 mm |
| depth | 90 mm |
| forwards | 0 mm |
| backwards | 0 mm |
| upwards | 0 mm |
| downwards | 0 mm |
| relative humidity during operation maximum | 70 % |
| last modified: | 6/30/2026 |