Especificaciones técnicas
Protección y seguridad
| Reverse polarity protection | Yes |
|---|---|
| Isolation tested with | 707 V DC (type test) |
Datos eléctricos
| Current consumption, max. | 90 mA |
|---|---|
| Power loss, typ. | 1.7 W |
| permissible quiescent current (2-wire sensor), max. | 1.5 mA |
| Monitoring the supply voltage | Yes |
| Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Entradas/Salidas y comunicación
| suitable for operation on PROFINET R1 IMs | Yes |
|---|---|
| PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
| PROFINET from GSD version/GSD revision | GSDML V2.3 |
Detección y sensórica
| 2-wire sensor | Yes |
|---|
Montaje y material
| Color code for module-specific color-coded label | CC00 |
|---|
Condiciones ambientales
| Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
|---|
Certificados y homologaciones
| Type Examination Cer | Miscellaneous |
|---|
Otras características
| Product type designation | DI 16x24VDC ST |
|---|---|
| HW functional status | From FS02 |
| Firmware version | V0.0 |
| usable BaseUnits | BU type A0 |
| I&M data | Yes; I&M0 to I&M3 |
| STEP 7 TIA Portal configurable/integrated from version | V14 |
| STEP 7 configurable/integrated from version | V5.5 SP3 |
| PCS 7 configurable/integrated from version | V8.1 SP1 |
| PCS neo can be configured/integrated from version | from V1.0.0 |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Inputs | 2 byte; + 2 bytes for QI information |
| Automatic encoding | Yes |
| Mechanical coding element | Yes |
| Type of mechanical coding element | Type A |
| 1-wire connection | BU type A0 |
| 2-wire connection | BU type A0 + Potential distributor module |
| 3-wire connection | BU type A0 + Potential distributor module |
| 4-wire connection | BU type A0 + Potential distributor module |
| Number of digital inputs | 16 |
| Digital inputs, parameterizable | Yes |
| Sourcing/sinking input | P-reading |
| for signal "0" | -30 to +5 V |
| for signal "1" | +11 to +30V |
| for signal "1", typ. | 2.5 mA |
| shielded, max. | 1 000 m |
| unshielded, max. | 600 m |
| Diagnostics function | Yes |
| Diagnostic alarm | Yes |
| Diagnostic information readable | Yes |
| parameterizable | Yes |
| Group error | Yes |
| Channel status display | Yes; green LED |
| for module diagnostics | Yes; green/red DIAG LED |
| between the channels and backplane bus | Yes |
| horizontal installation, min. | -30 °C; < 0 °C as of FS02 |
| horizontal installation, max. | 60 °C |
| vertical installation, min. | -30 °C; < 0 °C as of FS02 |
| vertical installation, max. | 50 °C |
| dew point, min. | -60 °C; suitable for dry room applications |
| Width | 15 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Weight, approx. | 28 g |
| last modified: | 2/1/2026 |