SIPLUS ET 200SP F-PM-E 24VDC/8A PPM RAIL
Siemens

SIPLUS ET 200SP F-PM-E 24VDC/8A PPM RAIL

SIPLUS ET 200SP F-PM-E 24 V DC/8 A PPM RAIL basado en 6ES7136-6PA00-0BC0 con revestimiento conformado, –30…+60 °C, OT1 con ST1/2 (+70 °C durante 10 min), módulo de potencia de seguridad PROFIsafe, 24 V DC, desconexión segura de DQ y F-DQ hasta PL D/SIL2 o PL E/SIL3 2 entradas digitales seguras 1 salida digital segura PPM

Protección y seguridad
Reverse polarity protectionYes
Short-circuit protectionYes; Electronic (response threshold 0.7 A to 2.1 A)
Overload protectionYes
Isolation tested with750 V DC (type test) and according to EN 50155 (routine test)
Performance level according to ISO 13849-1PLe
SIL acc. to IEC 61508SIL 3
Fire protection acc. to EN 45545-2Yes; For proof of conformity, see Service & Support
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Datos eléctricos
Current consumption (rated value)75 mA; without load
Current consumption, max.21 mA; From the backplane bus
Output current, max.600 mA; Total current of all encoders
Power consumption from the backplane bus70 mW
Power loss, typ.5W
Type of input voltageDC
Limitation of inductive shutdown voltage tomax. 1.5 V
for signal "0" residual current, max.1.5 mA; PP-switching: max. 1.5 mA; PM-switching: max. 1 mA
Current per channel, max.8 A; note derating data in the manual
Current per module, max.8 A; note derating data in the manual
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Montaje y material
Color code for module-specific color-coded labelCC52
Condiciones ambientales
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Certificados y homologaciones
China RoHSTUEV
Otras características
Product type designationF-PM-E PPM 24VDC
based on6ES7136-6PA00-0BC0
usable BaseUnitsBU type C0
I&M dataYes; I&M0 to I&M3
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Number of outputs2
up to 60 °C, max.0.3 A
24 VYes; min. L+ (-1.5 V)
Inputs7 byte
Outputs5 byte
Automatic encodingYes
Electronic coding element type FYes
Number of digital inputs2
Sourcing/sinking inputYes; P-reading
for signal "0"-30 to +5 V
for signal "1"+15 to +30 V
for signal "1", typ.3.7 mA
parameterizableYes
shielded, max.1 000 m
unshielded, max.500 m
Number of digital outputs1
Digital outputs, parameterizableYes
Response threshold, typ.> 14.8 A
Open-circuit detectionYes
lower limit3Ω
upper limit2 000 Ω
for signal "1", min.24 V; L+ (-0.5 V)
for signal "1" rated value8A
up to 40 °C, max.8 A; note derating data in the manual
up to 50 °C, max.6 A; note derating data in the manual
Diagnostics functionYes; See Chapter "Alarms/diagnostic messages" in the manual
Diagnostic alarmYes
RUN LEDYes; green LED
ERROR LEDYes; red LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; green/red DIAG LED
between the channels and backplane busYes
Suitable for safety functionsYes
50716specific application under consideration of all local regulations.
Low demand mode: PFDavg in accordance with< 2.00E-04
High demand/continuous mode: PFH in accordance< 1.00E-08 1/h
EN 50121-3-2Yes; EMC for rail vehicles
EN 50121-4Yes; EMC for signal and telecommunications systems
EN 50125-1Yes; Rail vehicles - see ambient conditions
EN 50125-2Yes; Stationary electrical equipment - see ambient conditions
EN 50125-3Yes; Signal and telecommunications systems - see ambient conditions;
EN 61373Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B
horizontal installation, min.-30 °C; = Tmin (incl. condensation/frost)
vertical installation, min.-30 °C; = Tmin
vertical installation, max.50 °C; = Tmax
2-38, max.horizontal installation
Resistant to commercially available coolants andYes; Incl. diesel and oil droplets in the air
60721-3-3Class 3B3 on request
to EN 60721-3-30AA0)
60721-3-5Class 5B3 on request
to EN 60721-3-50AA0)
agriculture acc. to ISO 15003(6AG1193-6AA00-0AA0)
conditions acc. to EN 60721, EN 60654-4 andduring operation!
Electronic equipment on rolling stock acc. to EN 50155Yes; Class PC2 protective coating acc. to EN 50155:2017
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical InsulatingYes; Conformal coating, Class A
Width20 mm
Height72 mm
Depth55 mm
Weight, approx.70 g
EMVFunctional Saftey
RailwayEnvironment
TUEVConfirmation
last modified:10/23/2025

Ficha técnica oficial del fabricante con todas las especificaciones.

Producto bajo pedido

Puedes pedirlo ya: te lo servimos en el plazo indicado. Selecciona la cantidad para añadirlo al carrito.

Plazo de entrega (días):
Avísame cuando haya stock