SITOP PSU6200/3AC/DC24V/20A
Siemens

SITOP PSU6200/3AC/DC24V/20A

SITOP PSU6200 24 V/20 A Fuente de alimentación estabilizada Entrada: 400-500 V AC Salida: 24 V DC/20 A con interfaz de diagnóstico

Medición y rango
relative control precision of the output voltage at load step of3%
Otras características
type of the power supply network3-phase AC or DC
minimum rated value400 V
maximum rated value500 V
initial value323 V
full-scale value576 V
supply voltage at DC500 ... 550 V
input voltage at DC450 ... 600 V
operating condition of the mains bufferingat Vin = 400 V
line frequency50/60 Hz
at rated input voltage 400 V0.77 A
at rated input voltage 500 V0.62 A
current limitation of inrush current at 25 °C maximum17 A
fuse protection type in the feederthree-poled coupled circuit breaker from 4 A characteristic C to 16 A
voltage curve at outputControlled, isolated DC voltage
number of outputs1
output voltage at DC rated value24 V
at output 1 at DC rated value24 V
output voltage adjustableYes; via potentiometer
adjustable output voltage24 ... 28 V; max. 480 W (576 W up to 45°C)
relative overall tolerance of the voltage3%
on slow fluctuation of input voltage0.2 %
on slow fluctuation of ohm loading0.1 %
maximum30 mV
typical20 mV
display version for normal operationGreen LED for 24 V OK
behavior of the output voltage when switching onOvershoot of Vout < 2 %
response delay maximum0.5 s
rated value20 A
rated range0 ... 20 A; 24 A up to +45°C; +60 ... +70 °C: Derating 3%/K
supplied active power typical480 W
on short-circuiting during the start-up typical24 A
at short-circuit during operation typical24 A
parallel switching of outputscan be set with DIP switch
bridging of equipmentYes; switchable characteristic
efficiency in percent95.9 %
at rated output voltage for rated value of the output23 W
during no-load operation maximum2.9 W
load step 10 to 90% typical2 ms
load step 90 to 10% typical2 ms
design of the overvoltage protection< 32 V
property of the output short-circuit proofYes
design of short-circuit protectionShutdown and periodic restart attempts
in normal operationoverload capability 150 % Iout rated up to 5 s/min
galvanic isolation between input and outputYes
galvanic isolationOutput voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection classClass I
protection class IPIP20
for emitted interferenceEN 55022 Class B
for mains harmonics limitationEN 61000-3-2
for interference immunityEN 61000-6-2
CE markingYes
UL approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
UKCA markingYes
EAC approvalYes
Regulatory Compliance Mark (RCM)Yes
SEMI F47Yes
BISYes; R-41188271
CB-certificateYes
shipbuilding approvalYes
American Bureau of Shipping Europe Ltd. (ABS)Yes
Det Norske Veritas (DNV)Yes
total621.62 kg
during manufacturing38.5 kg
during operation582 kg
during transport-40 ... +85 °C
during storage-40 ... +85 °C
type of electrical connectionpush-in terminals
at inputL1, L2, L3, PE: push-in for 0.5 ... 10 mm²
at output+1, +2, -1, -2, -3: push-in for 0.5 ... 6 mm²
for auxiliary contacts13, 14 (alarm signal): 1 push-in terminal each for 0.2 ... 1.5 mm²
width × height × depth of the enclosure70 × 135 × 155 mm
installation width × mounting height70 mm × 225 mm
top45 mm
bottom45 mm
left0 mm
right0 mm
fastening methodSnaps onto DIN rail EN 60715 35x7.5/15
DIN-rail mountingYes
housing can be lined upYes
net weight1.5 kg
electrical accessoriesBuffer module, redundancy module
mechanical accessoriesIdentification labels SIMATIC ET 200SP 6ES7193-6LF30-0AW0
identification linkYes; acc. to IEC 61406-1:2022
IDEA4
UNSPSC15
last modified:5/21/2026
⬇ Descargar datasheet (PDF)

Ficha técnica oficial del fabricante con todas las especificaciones.

Material con posibilidad de devolución
SITOP PSU6200/3AC/DC24V/20A
€224,03 EUR
€320,04 EUR
6EP3436-7SB00-3AX0
Plazo de entrega (días):
€224,03 EUR /each
Total:

Accesorios