Especificaciones técnicas
Protección y seguridad
| Reverse polarity protection | Yes |
|---|---|
| Short-circuit protection | Yes; Electronic |
| Short-circuit to ground | Yes; channel by channel |
| Short-circuit to L+ | Yes; channel by channel |
| Isolation tested with | 707 V DC (type test) |
| Performance level according to ISO 13849-1 | PL d |
| SIL acc. to IEC 61508 | SIL 2 |
Datos eléctricos
| Current consumption (rated value) | 28 mA |
|---|---|
| Current consumption, max. | 28 mA |
| Power loss, typ. | 1W |
| Current-sourcing | Yes |
| Limitation of inductive shutdown voltage to | L+ -(37 to 41V) |
| for signal "0" residual current, max. | 0.1 mA |
| Current per channel, max. | 2A |
| Current per module, max. | 8A |
| Monitoring the supply voltage | Yes |
| Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Entradas/Salidas y comunicación
| PROFIBUS from GSD version/GSD revision | GSD Revision 5 |
|---|---|
| PROFINET from GSD version/GSD revision | GSDML V2.3 |
Montaje y material
| Color code for module-specific color-coded label | CC02 |
|---|
Condiciones ambientales
| Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
|---|
Certificados y homologaciones
| Type Examination Cer | Miscellaneous |
|---|
Otras características
| Product type designation | DQ 4x DC 24 V/2 A HF |
|---|---|
| HW functional status | FS20 or higher |
| Firmware version | V2.0.3 |
| FW update possible | Yes |
| usable BaseUnits | BU type A0 |
| I&M data | Yes; I&M0 to I&M3 |
| Isochronous mode | Yes; 250 µs |
| STEP 7 TIA Portal configurable/integrated from version | V13 SP1 / - |
| STEP 7 configurable/integrated from version | V5.5 / - |
| MSO | Yes |
| Rated value (DC) | 24 V |
| permissible range, lower limit (DC) | 19.2 V |
| permissible range, upper limit (DC) | 28.8 V |
| Address space per module, max. | 4 byte; 2 channels per submodule + QI information |
| Automatic encoding | Yes |
| Mechanical coding element | Yes |
| Type of mechanical coding element | Type A |
| 1-wire connection | BU type A0 |
| 2-wire connection | BU type A0 |
| 3-wire connection | BU type A0 with AUX terminals or potential distributor module |
| 4-wire connection | BU type A0 + Potential distributor module |
| Type of digital output | Source output (PNP, current-sourcing) |
| Number of digital outputs | 4 |
| Digital outputs, parameterizable | Yes |
| output type acc. to IEC 61131, type 2 | Yes |
| Response threshold, typ. | 2.8 to 5.2 A |
| Controlling a digital input | Yes; Minimum current consumption 7 mA |
| lower limit | 12 Ω |
| upper limit | 3 400 Ω |
| for signal "1" rated value | 2A |
| "0" to "1", typ. | 50 µs |
| "1" to "0", typ. | 100 µs |
| up to 40 °C, max. | 8A |
| up to 50 °C, max. | 6A |
| up to 60 °C, max. | 4A |
| up to 30 °C, max. | 8A |
| shielded, max. | 1 000 m |
| unshielded, max. | 600 m |
| Bus cycle time (TDP), min. | 500 µs |
| Jitter, max. | 8 µs |
| Diagnostics function | Yes |
| Substitute values connectable | Yes |
| Diagnostic alarm | Yes |
| Wire break | Yes; channel by channel |
| Group error | Yes |
| Channel status display | Yes; green LED |
| for channel diagnostics | Yes; red LED |
| for module diagnostics | Yes; green/red DIAG LED |
| between the channels and backplane bus | Yes |
| horizontal installation, min. | -30 °C; < 0 °C as of FS06 |
| horizontal installation, max. | 60 °C |
| vertical installation, min. | -30 °C; < 0 °C as of FS06 |
| vertical installation, max. | 50 °C |
| Width | 15 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Weight, approx. | 30 g |
| last modified: | 10/23/2025 |