| Product type designation | CPU 1512SP F-1 PN |
|---|
| based on | 6ES7512-1SK01-0AB0 |
|---|
| I&M data | Yes; I&M0 to I&M3 |
|---|
| Module swapping during operation (hot swapping) | Yes; Multi-hot swapping |
|---|
| Isochronous mode | Yes; Only with PROFINET; with minimum OB 6x cycle of 625 µs |
|---|
| STEP 7 TIA Portal configurable/integrated from version | see entry ID: 109746275 |
|---|
| via dataset | Yes |
|---|
| Mode selector switch | 1 |
|---|
| Rated value (DC) | 24 V |
|---|
| permissible range, lower limit (DC) | 19.2 V |
|---|
| permissible range, upper limit (DC) | 28.8 V |
|---|
| Reverse polarity protection | Yes |
|---|
| Mains/voltage failure stored energy time | 5 ms |
|---|
| Current consumption (rated value) | 0.6 A |
|---|
| Current consumption, max. | 0.9 A |
|---|
| Inrush current, max. | 4.7 A; Rated value |
|---|
| I²t | 0.14 A²·s |
|---|
| Infeed power to the backplane bus | 8.75 W |
|---|
| Power loss, typ. | 5.6 W |
|---|
| Number of slots for SIMATIC memory card | 1 |
|---|
| SIMATIC memory card required | Yes |
|---|
| integrated (for program) | 300 kbyte |
|---|
| integrated (for data) | 1 Mbyte |
|---|
| Plug-in (SIMATIC Memory Card), max. | 32 Gbyte |
|---|
| maintenance-free | Yes |
|---|
| for bit operations, typ. | 48 ns |
|---|
| for word operations, typ. | 58 ns |
|---|
| for fixed point arithmetic, typ. | 77 ns |
|---|
| for floating point arithmetic, typ. | 307 ns |
|---|
| Number of elements (total) | 4 000; Blocks (OB, FB, FC, DB) and UDTs |
|---|
| Size, max. | 1 Mbyte; For DBs with absolute addressing, the max. size is 64 KB |
|---|
| Number range | 0 ... 65 535 |
|---|
| Number of free cycle OBs | 100 |
|---|
| Number of time alarm OBs | 20 |
|---|
| Number of delay alarm OBs | 20 |
|---|
| Number of cyclic interrupt OBs | 20; With minimum OB 3x cycle of 500 µs |
|---|
| Number of process alarm OBs | 50 |
|---|
| Number of DPV1 alarm OBs | 3 |
|---|
| Number of isochronous mode OBs | 1 |
|---|
| Number of technology synchronous alarm OBs | 2 |
|---|
| Number of startup OBs | 100 |
|---|
| Number of asynchronous error OBs | 4 |
|---|
| Number of synchronous error OBs | 2 |
|---|
| Number of diagnostic alarm OBs | 1 |
|---|
| per priority class | 24; Up to 8 possible for F-blocks |
|---|
| Number | 2 048 |
|---|
| can be set | Yes |
|---|
| adjustable | Yes |
|---|
| Number of clock memories | 8; 8 clock memory bit, grouped into one clock memory byte |
|---|
| Retentivity adjustable | Yes |
|---|
| per priority class, max. | 64 kbyte; max. 16 KB per block |
|---|
| Number of IO modules | 2 048; max. number of modules / submodules |
|---|
| Inputs | 32 kbyte; All inputs are in the process image |
|---|
| Outputs | 32 kbyte; All outputs are in the process image |
|---|
| Inputs (volume) | 8 kbyte |
|---|
| Outputs (volume) | 8 kbyte |
|---|
| Number of subprocess images, max. | 32 |
|---|
| Address space per module, max. | 288 byte; For input and output data respectively |
|---|
| Via CM | 1 |
|---|
| Integrated | 1 |
|---|
| via CM | 0 |
|---|
| Modules per rack, max. | 80; CPU + 64 modules + server module (mounting width max. 1 m) + 16 ET |
|---|
| Quantity of operable ET 200SP modules, max. | 64 |
|---|
| Quantity of operable ET 200AL modules, max. | 16 |
|---|
| Number of lines, max. | 1 |
|---|
| Type | Hardware clock |
|---|
| Backup time | 6 wk; At 40 °C ambient temperature, typically |
|---|
| Deviation per day, max. | 10 s; Typ.: 2 s |
|---|
| supported | Yes |
|---|
| to DP, master | Yes; Via CM DP module |
|---|
| on DP, device | Yes; Via CM DP module |
|---|
| in AS, master | Yes |
|---|
| in AS, device | Yes |
|---|
| Number of ports | 3; 1. integr. + 2. via BusAdapter |
|---|
| integrated switch | Yes |
|---|
| IP protocol | Yes; IPv4 |
|---|
| SIMATIC communication | Yes |
|---|
| Open IE communication | Yes; Optionally also encrypted |
|---|
| Web server | Yes |
|---|
| Media redundancy | Yes; MRP Automanager according to IEC 62439-2 Edition 2.0 |
|---|
| PG/OP communication | Yes |
|---|
| Direct data exchange | Yes; Requirement: IRT and isochronous mode (MRPD optional) |
|---|
| IRT | Yes |
|---|
| PROFIenergy | Yes; per user program |
|---|
| Prioritized startup | Yes; Max. 32 PROFINET devices |
|---|
| Of which IO devices with IRT, max. | 64 |
|---|
| Number of connectable IO Devices for RT, max. | 128 |
|---|
| of which in line, max. | 128 |
|---|
| Number of IO Devices that can be simultaneously | 8; in total across all interfaces |
|---|
| Number of IO Devices per tool, max. | 8 |
|---|
| for send cycle of 500 µs | 500 µs to 8 ms |
|---|
| for send cycle of 1 ms | 1 ms to 16 ms |
|---|
| for send cycle of 2 ms | 2 ms to 32 ms |
|---|
| for send cycle of 4 ms | 4 ms to 64 ms |
|---|
| for send cycle of 250 µs | 250 µs to 128 ms |
|---|
| Shared device | Yes |
|---|
| Number of IO Controllers with shared device, max. | 4 |
|---|
| activation/deactivation of I-devices | Yes; per user program |
|---|
| Asset management record | Yes; per user program |
|---|
| RS 485 | Yes; Via CM DP module |
|---|
| Number of connections, max. | 48; Of which 4 each reserved for ES and HMI |
|---|
| activation/deactivation of DP devices | Yes |
|---|
| 100 Mbps | Yes |
|---|
| Autonegotiation | Yes |
|---|
| Autocrossing | Yes |
|---|
| Transmission rate, max. | 12 Mbit/s |
|---|
| Number of connections reserved for ES/HMI/web | 10 |
|---|
| Number of connections per CP/CM | 32 |
|---|
| Number of S7 routing paths | 16 |
|---|
| H-Sync forwarding | Yes |
|---|
| MRP interconnection, supported | Yes; as MRP ring node according to IEC 62439-2 Edition 3.0 |
|---|
| MRPD | Yes; Requirement: IRT |
|---|
| Switchover time on line break, typ. | 200 ms; For MRP, bumpless for MRPD |
|---|
| Number of stations in the ring, max. | 50 |
|---|
| S7 routing | Yes |
|---|
| Data record routing | Yes |
|---|
| S7 communication, as server | Yes |
|---|
| S7 communication, as client | Yes |
|---|
| User data per job, max. | See online help (S7 communication, user data size) |
|---|
| TCP/IP | Yes |
|---|
| Data length, max. | 64 kbyte |
|---|
| several passive connections per port, supported | Yes |
|---|
| ISO-on-TCP (RFC1006) | Yes |
|---|
| UDP | Yes |
|---|
| UDP multicast | Yes; Max. 5 multicast circuits |
|---|
| DHCP | Yes |
|---|
| DNS | Yes |
|---|
| SNMP | Yes |
|---|
| DCP | Yes |
|---|
| LLDP | Yes |
|---|
| encryption | Yes; Optional |
|---|
| HTTP | Yes; Standard and user pages |
|---|
| HTTPS | Yes; Standard and user pages |
|---|
| Runtime license required | Yes |
|---|
| Application authentication | Yes |
|---|
| Security policies | Available security policies: None, Basic128Rsa15, Basic256Rsa15, |
|---|
| User authentication | "anonymous" or by user name & password |
|---|
| Number of elements for one call of | 300 |
|---|
| Number of simultaneous calls of the client | 1 |
|---|
| Number of registerable nodes, max. | 5 000 |
|---|
| Number of registerable method calls of | 100 |
|---|
| Number of inputs/outputs when calling | 20 |
|---|
| Number of sessions, max. | 32 |
|---|
| Number of accessible variables, max. | 50 000 |
|---|
| Number of subscriptions per session, max. | 20 |
|---|
| Sampling interval, min. | 100 ms |
|---|
| Publishing interval, min. | 500 ms |
|---|
| Number of server methods, max. | 20 |
|---|
| Number of inputs/outputs per server method, max. | 20 |
|---|
| Number of monitored items, recommended max. | 1 000; for 1 s sampling interval and 1 s send interval |
|---|
| Number of login stations for message functions, max. | 32 |
|---|
| Program alarms | Yes |
|---|
| Number of configurable program messages, max. | 5 000; Program messages are generated by the "Program_Alarm" block, |
|---|
| Number of loadable program messages in RUN, max. | 2 500 |
|---|
| Number of program alarms | 600 |
|---|
| Number of alarms for system diagnostics | 100 |
|---|
| Number of alarms for motion technology objects | 80 |
|---|
| Joint commission (Team Engineering) | Yes; Parallel online access possible for up to 5 engineering systems |
|---|
| Status block | Yes; Up to 8 simultaneously (in total across all ES clients) |
|---|
| Number of breakpoints | 8 |
|---|
| Status/control variable | Yes; without fail-safe |
|---|
| Variables | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters |
|---|
| of which status variables, max. | 200; per job |
|---|
| of which control variables, max. | 200; per job |
|---|
| Forcing | Yes; without fail-safe |
|---|
| Forcing, variables | Peripheral inputs/outputs |
|---|
| Number of variables, max. | 200 |
|---|
| present | Yes |
|---|
| Number of entries, max. | 1 000 |
|---|
| of which powerfail-proof | 500 |
|---|
| Number of configurable Traces | 4; Up to 512 KB of data per trace are possible |
|---|
| RUN/STOP LED | Yes |
|---|
| ERROR LED | Yes |
|---|
| MAINT LED | Yes |
|---|
| Monitoring of the supply voltage (PWR-LED) | Yes |
|---|
| Connection display LINK TX/RX | Yes |
|---|
| Number of available Motion Control resources for | 800 |
|---|
| per speed-controlled axis | 40 |
|---|
| per positioning axis | 80 |
|---|
| per synchronous axis | 160 |
|---|
| per external encoder | 80 |
|---|
| per output cam | 20 |
|---|
| per cam track | 160 |
|---|
| per probe | 40 |
|---|
| Number of positioning axes at motion control cycle | 5 |
|---|
| PID_Compact | Yes; Universal PID controller with integrated optimization |
|---|
| PID_3Step | Yes; PID controller with integrated optimization for valves |
|---|
| PID-Temp | Yes; PID controller with integrated optimization for temperature |
|---|
| High-speed counter | Yes |
|---|
| Low demand mode: PFDavg in accordance with | < 2.00E-05 |
|---|
| High demand/continuous mode: PFH in accordance | < 1.00E-09 |
|---|
| horizontal installation, min. | -25 °C; = Tmin (incl. condensation/frost) |
|---|
| horizontal installation, max. | 60 °C; = Tmax |
|---|
| vertical installation, min. | -25 °C; = Tmin |
|---|
| vertical installation, max. | 50 °C; = Tmax |
|---|
| 2-38, max. | horizontal installation |
|---|
| Resistant to commercially available coolants and | Yes; Incl. diesel and oil droplets in the air |
|---|
| 60721-3-3 | Class 3B3 on request |
|---|
| to EN 60721-3-3 | 0AA0) |
|---|
| to EN 60721-3-5 | 0AA0) |
|---|
| agriculture acc. to ISO 15003 | (6AG1193-6AA00-0AA0) |
|---|
| 60721-3-6 | degree 3); * |
|---|
| to EN 60721-3-6 | 0AA0) |
|---|
| conditions acc. to EN 60721, EN 60654-4 and | during operation! |
|---|
| Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection |
|---|
| Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life |
|---|
| Qualification and Performance of Electrical Insulating | Yes; Conformal coating, Class A |
|---|
| LAD | Yes; incl. failsafe |
|---|
| FBD | Yes; incl. failsafe |
|---|
| STL | Yes |
|---|
| SCL | Yes |
|---|
| GRAPH | Yes |
|---|
| User program protection/password protection | Yes |
|---|
| Copy protection | Yes |
|---|
| Block protection | Yes |
|---|
| Protection level: Write protection | Yes |
|---|
| Protection level: Read/write protection | Yes |
|---|
| Protection level: Complete protection | Yes |
|---|
| lower limit | adjustable minimum cycle time |
|---|
| upper limit | adjustable maximum cycle time |
|---|
| Width | 100 mm |
|---|
| Height | 117 mm |
|---|
| Depth | 75 mm |
|---|
| Weight, approx. | 310 g |
|---|
| IDEA | 4 |
|---|
| UNSPSC | 15 |
|---|
| Functional Saftey | Maritime application |
|---|
| TUEV | TUEV |
|---|
| last modified: | 12/8/2024 |
|---|