SIPLUS ET 200SP CPU 1512SP F-1PN
Certificados y homologaciones
EAC
Siemens

SIPLUS ET 200SP CPU 1512SP F-1PN

Producto descatalogado No disponible para compra · sin producto de reemplazo.
SIPLUS ET 200SP CPU 1512SP F-1 PN basado en 6ES7512-1SK01-0AB0 con revestimiento conformado, –25…+60 °C, módulo central con memoria de trabajo de 300 kB para programa y 1 MB para datos, 1.ª interfaz, PROFINET IRT con switch de 3 puertos, 48 NS rendimiento bits, SIMATIC Memory Card necesaria, adaptador de bus necesario para puertos 1 y 2

  • Comunicación1
Protección y seguridad
Performance level according to ISO 13849-1PLe
SIL acc. to IEC 61508SIL 3
Entradas/Salidas y comunicación
on Ethernet via NTPYes
Number of PROFINET interfaces1
Number of PROFIBUS interfaces1; Via CM DP module
Optical interfaceYes; via BusAdapter
RJ 45 (Ethernet)Yes; X1 P3; opt. X1 P1 and X1 P2 via BusAdapter BA 2x RJ45
BusAdapter (PROFINET)Yes; compatible BusAdapters: BA 2x RJ45, BA 2x FC, BA 2x M12
PROFINET IO ControllerYes
PROFINET IO deviceYes
PROFIBUS DP masterYes
PROFIBUS DP deviceYes
Industrial Ethernet status LEDYes
PROFIsafeYes; V2.4 / V2.6
Number of connections via integrated interfaces88
OPC UA ClientYes
Number of nodes of the client interfaces,1 000
Number of nodes for user-defined server interfaces,1 000
MODBUSYes; MODBUS TCP
Condiciones ambientales
Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Otras características
Product type designationCPU 1512SP F-1 PN
based on6ES7512-1SK01-0AB0
I&M dataYes; I&M0 to I&M3
Module swapping during operation (hot swapping)Yes; Multi-hot swapping
Isochronous modeYes; Only with PROFINET; with minimum OB 6x cycle of 625 µs
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
via datasetYes
Mode selector switch1
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Mains/voltage failure stored energy time5 ms
Current consumption (rated value)0.6 A
Current consumption, max.0.9 A
Inrush current, max.4.7 A; Rated value
I²t0.14 A²·s
Infeed power to the backplane bus8.75 W
Power loss, typ.5.6 W
Number of slots for SIMATIC memory card1
SIMATIC memory card requiredYes
integrated (for program)300 kbyte
integrated (for data)1 Mbyte
Plug-in (SIMATIC Memory Card), max.32 Gbyte
maintenance-freeYes
for bit operations, typ.48 ns
for word operations, typ.58 ns
for fixed point arithmetic, typ.77 ns
for floating point arithmetic, typ.307 ns
Number of elements (total)4 000; Blocks (OB, FB, FC, DB) and UDTs
Size, max.1 Mbyte; For DBs with absolute addressing, the max. size is 64 KB
Number range0 ... 65 535
Number of free cycle OBs100
Number of time alarm OBs20
Number of delay alarm OBs20
Number of cyclic interrupt OBs20; With minimum OB 3x cycle of 500 µs
Number of process alarm OBs50
Number of DPV1 alarm OBs3
Number of isochronous mode OBs1
Number of technology synchronous alarm OBs2
Number of startup OBs100
Number of asynchronous error OBs4
Number of synchronous error OBs2
Number of diagnostic alarm OBs1
per priority class24; Up to 8 possible for F-blocks
Number2 048
can be setYes
adjustableYes
Number of clock memories8; 8 clock memory bit, grouped into one clock memory byte
Retentivity adjustableYes
per priority class, max.64 kbyte; max. 16 KB per block
Number of IO modules2 048; max. number of modules / submodules
Inputs32 kbyte; All inputs are in the process image
Outputs32 kbyte; All outputs are in the process image
Inputs (volume)8 kbyte
Outputs (volume)8 kbyte
Number of subprocess images, max.32
Address space per module, max.288 byte; For input and output data respectively
Via CM1
Integrated1
via CM0
Modules per rack, max.80; CPU + 64 modules + server module (mounting width max. 1 m) + 16 ET
Quantity of operable ET 200SP modules, max.64
Quantity of operable ET 200AL modules, max.16
Number of lines, max.1
TypeHardware clock
Backup time6 wk; At 40 °C ambient temperature, typically
Deviation per day, max.10 s; Typ.: 2 s
supportedYes
to DP, masterYes; Via CM DP module
on DP, deviceYes; Via CM DP module
in AS, masterYes
in AS, deviceYes
Number of ports3; 1. integr. + 2. via BusAdapter
integrated switchYes
IP protocolYes; IPv4
SIMATIC communicationYes
Open IE communicationYes; Optionally also encrypted
Web serverYes
Media redundancyYes; MRP Automanager according to IEC 62439-2 Edition 2.0
PG/OP communicationYes
Direct data exchangeYes; Requirement: IRT and isochronous mode (MRPD optional)
IRTYes
PROFIenergyYes; per user program
Prioritized startupYes; Max. 32 PROFINET devices
Of which IO devices with IRT, max.64
Number of connectable IO Devices for RT, max.128
of which in line, max.128
Number of IO Devices that can be simultaneously8; in total across all interfaces
Number of IO Devices per tool, max.8
for send cycle of 500 µs500 µs to 8 ms
for send cycle of 1 ms1 ms to 16 ms
for send cycle of 2 ms2 ms to 32 ms
for send cycle of 4 ms4 ms to 64 ms
for send cycle of 250 µs250 µs to 128 ms
Shared deviceYes
Number of IO Controllers with shared device, max.4
activation/deactivation of I-devicesYes; per user program
Asset management recordYes; per user program
RS 485Yes; Via CM DP module
Number of connections, max.48; Of which 4 each reserved for ES and HMI
activation/deactivation of DP devicesYes
100 MbpsYes
AutonegotiationYes
AutocrossingYes
Transmission rate, max.12 Mbit/s
Number of connections reserved for ES/HMI/web10
Number of connections per CP/CM32
Number of S7 routing paths16
H-Sync forwardingYes
MRP interconnection, supportedYes; as MRP ring node according to IEC 62439-2 Edition 3.0
MRPDYes; Requirement: IRT
Switchover time on line break, typ.200 ms; For MRP, bumpless for MRPD
Number of stations in the ring, max.50
S7 routingYes
Data record routingYes
S7 communication, as serverYes
S7 communication, as clientYes
User data per job, max.See online help (S7 communication, user data size)
TCP/IPYes
Data length, max.64 kbyte
several passive connections per port, supportedYes
ISO-on-TCP (RFC1006)Yes
UDPYes
UDP multicastYes; Max. 5 multicast circuits
DHCPYes
DNSYes
SNMPYes
DCPYes
LLDPYes
encryptionYes; Optional
HTTPYes; Standard and user pages
HTTPSYes; Standard and user pages
Runtime license requiredYes
Application authenticationYes
Security policiesAvailable security policies: None, Basic128Rsa15, Basic256Rsa15,
User authentication"anonymous" or by user name & password
Number of elements for one call of300
Number of simultaneous calls of the client1
Number of registerable nodes, max.5 000
Number of registerable method calls of100
Number of inputs/outputs when calling20
Number of sessions, max.32
Number of accessible variables, max.50 000
Number of subscriptions per session, max.20
Sampling interval, min.100 ms
Publishing interval, min.500 ms
Number of server methods, max.20
Number of inputs/outputs per server method, max.20
Number of monitored items, recommended max.1 000; for 1 s sampling interval and 1 s send interval
Number of login stations for message functions, max.32
Program alarmsYes
Number of configurable program messages, max.5 000; Program messages are generated by the "Program_Alarm" block,
Number of loadable program messages in RUN, max.2 500
Number of program alarms600
Number of alarms for system diagnostics100
Number of alarms for motion technology objects80
Joint commission (Team Engineering)Yes; Parallel online access possible for up to 5 engineering systems
Status blockYes; Up to 8 simultaneously (in total across all ES clients)
Number of breakpoints8
Status/control variableYes; without fail-safe
VariablesInputs/outputs, memory bits, DBs, distributed I/Os, timers, counters
of which status variables, max.200; per job
of which control variables, max.200; per job
ForcingYes; without fail-safe
Forcing, variablesPeripheral inputs/outputs
Number of variables, max.200
presentYes
Number of entries, max.1 000
of which powerfail-proof500
Number of configurable Traces4; Up to 512 KB of data per trace are possible
RUN/STOP LEDYes
ERROR LEDYes
MAINT LEDYes
Monitoring of the supply voltage (PWR-LED)Yes
Connection display LINK TX/RXYes
Number of available Motion Control resources for800
per speed-controlled axis40
per positioning axis80
per synchronous axis160
per external encoder80
per output cam20
per cam track160
per probe40
Number of positioning axes at motion control cycle5
PID_CompactYes; Universal PID controller with integrated optimization
PID_3StepYes; PID controller with integrated optimization for valves
PID-TempYes; PID controller with integrated optimization for temperature
High-speed counterYes
Low demand mode: PFDavg in accordance with< 2.00E-05
High demand/continuous mode: PFH in accordance< 1.00E-09
horizontal installation, min.-25 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.60 °C; = Tmax
vertical installation, min.-25 °C; = Tmin
vertical installation, max.50 °C; = Tmax
2-38, max.horizontal installation
Resistant to commercially available coolants andYes; Incl. diesel and oil droplets in the air
60721-3-3Class 3B3 on request
to EN 60721-3-30AA0)
to EN 60721-3-50AA0)
agriculture acc. to ISO 15003(6AG1193-6AA00-0AA0)
60721-3-6degree 3); *
to EN 60721-3-60AA0)
conditions acc. to EN 60721, EN 60654-4 andduring operation!
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical InsulatingYes; Conformal coating, Class A
LADYes; incl. failsafe
FBDYes; incl. failsafe
STLYes
SCLYes
GRAPHYes
User program protection/password protectionYes
Copy protectionYes
Block protectionYes
Protection level: Write protectionYes
Protection level: Read/write protectionYes
Protection level: Complete protectionYes
lower limitadjustable minimum cycle time
upper limitadjustable maximum cycle time
Width100 mm
Height117 mm
Depth75 mm
Weight, approx.310 g
IDEA4
UNSPSC15
Functional SafteyMaritime application
TUEVTUEV
last modified:12/8/2024

Ficha técnica oficial del fabricante con todas las especificaciones.

Producto bajo pedido

Puedes pedirlo ya: te lo servimos en el plazo indicado. Selecciona la cantidad para añadirlo al carrito. Si prefieres esperar a que vuelva a haber stock inmediato, déjanos tu email abajo.

Plazo de entrega (días):

Este artículo va bajo pedido.

Avísame cuando esté disponible

Solo usaremos tu email para avisarte de este artículo.

Accesorios